Viking VCSB5483 Installation Instruction

Page of 36
4
IMPORTANT – 
Please Read and Follow!
 A GFI shall be used if required by NFPA-70 (National Electric Code), federal/state/local 
laws, or local ordinances.
•  The required use of a GFI is normally related to the location of a receptacle with respect to  
 
 any 
signifi cant sources of water or moisture.
•  Viking Range, LLC will NOT warranty any problems resulting from GFI outlets which are not    
  installed properly or do not meet the requirements below.
If the use of a GFI is required, it should be:
•  Of the receptacle type (breaker type or portable type NOT recommended)
•  Used with permanent wiring only (temporary or portable wiring NOT recommended)
•  On a dedicated circuit (no other receptacles, switches or loads in the circuit)
•  Connected to a standard breaker of appropriate size (GFI breaker of the same size NOT  
 
 recommended)
•  Rated for Class A (5 mA +/- 1 mA trip current) as per UL 943 standard)
•  In good condition and free from any loose-fi tting gaskets (if applicable in outdoor situations)
•  Protected from moisture (water, steam, high humidity) as much as reasonably possible