GE ADER30LQ Owner's Manual

Page of 36
8
 
Troubleshooting tips…
Save time and money! Review the chart below first and you may not need to call for service.
Problem 
Possible Causes 
What To Do
Dehumidifier 
 
The dehumidifier  
tMake sure the dehumidifier’s plug is pushed completely 
does not start
 
is unplugged. 
  into the outlet.
 
The fuse is blown/circuit 
t Check the house fuse/circuit breaker box and replace
 
breaker is tripped. 
  the fuse or reset the breaker.
 
Dehumidifier has reached its  
t The dehumidifier automatically turns off when either
 
preset level or bucket is full.  
  condition occurs. Change to a lower setting or empty 
 
 
  the bucket and replace properly.
 
Bucket is not in the  
t The bucket must be in place and securely seated for the 
 
proper position. 
  dehumidifier to operate. 
 
Power failure. 
t There is a protective time delay (up to 3 minutes) to 
 
 
  prevent tripping of the compressor overload. For this  
 
 
  reason, the unit may not start normal dehumidifying  
 
 
  for 3 minutes after it is turned back on.
Dehumidifier does not
 
Did not allow enough time  
t When first installed, allow at least 24 hours to maintain 
dry the air as it should
 
to remove the moisture.  
  the desired dryness.
 
Airflow is restricted.  
t Make sure there are no curtains, blinds or furniture 
 
 
  blocking the front or back of the dehumidifier. See the  
 
 
  Choosing a Location section.
 
Dirty filter. 
t See the Care and Cleaning section.
 
The Humidity Control may  
t For drier air, press the ź pad and set to a lower percent    
 
not be set low enough.  
  value (%) or at CO (continuous) for maximum  
 
  
 
dehumidification.
 
Doors and windows may not  
t Check that all doors, windows and other openings 
 
be closed tightly.  
  are securely closed.
 
Clothes dryer may be  
t Install the dehumidifier away from the dryer. 
 
blowing moisture-laden  
  The dryer should be vented to the outside. 
 
air into the room. 
 
Room temperature  
t Moisture removal is best at higher room temperatures. 
 
is too low.  
  Lower room temperatures will reduce the moisture  
 
 
 
  removal rate. Models are designed to be operated at    
 
 
  temperatures above 41°F (5°C).
Dehumidifier runs
 
Area to be dehumidified  
t The capacity of your dehumidifier may not be adequate. 
too much
 
is too large.  
 
 
Doors and windows are open.  
t Close all doors and windows to the outside. 
Frost appears on 
 
Dehumidifier has been turned  
t This is normal. Frost will usually disappear 
the coils
 
on recently, or room temperature    within 60 minutes. See the Automatic Defrost section.
 
is below 41°F (5°C). 
Controls cannot be set 
The compressor will turn off  
t This is normal. Wait approximately 3 minutes and set the 
 
and the fan will automatically     fan as desired.
 
continue to run for 
 
approximately 3 minutes at a 
 fixed 
setting. 
Fan noise 
 
Air is moving through 
t This is normal. 
 
the dehumidifier.  
 
Water on floor
 
Hose connection may be loose.  t Check the hose connection. See the Removing Collected 
  
 
Water section. 
 
Intended to use the bucket to  
t Disconnect the hose if using the bucket to collect water. 
 
collect water, but a hose See 
the 
Removing Collected Water section
 
as attached.
Bucket Full LED light
  
Drain hose not tight on fitting 
t Check drain hose connection.
flashing and alarm 
 
 
sounds while drain hose  
 
Drain hose is kinked 
t Ensure the drain hose is pointed straight down to the floor 
is connected
 
 
and is not kinked in anyway.
Consumer Support
Troubleshooting Tips
Operating Instructions
Safety Instructions
Troubleshooting Tips
Care and Cleaning
Safety Instructions
Operating Instructions