GE HE500TIU050 User Manual
CH.1: INTRODUCTION 06 Apr 2000 PAGE 11
GFK-1819
1.3 Technical
Specifications
Table 1.2 – Technical Specifications
Parameter
Conditions
Min.
Typical
Max.
Units
Input voltage (V
I
)
10
24
32
VDC
Typical power consumption
TIU050
TIU10X
TIU11X
TIU20X
TIU10X
TIU11X
TIU20X
V
I
= 24VDC
V
I
= 24VDC
V
I
= 24VDC
V
I
= 24VDC
130
130
130
350
130
130
350
mA
Inrush input current
V
I
= 24VDC for 4ms
260
mA
Operating temperature
TIU050
TIU10X
TIU10X-6
TIU11X
TIU11X-6
TIU20XA
TIU20XB or higher
TIU10X
TIU10X-6
TIU11X
TIU11X-6
TIU20XA
TIU20XB or higher
0
0
0
-10
0
-10
0
0
0
50
50
60
50
60
45
50
50
60
50
60
45
50
°C
Storage temperature
-20
70
°C
Relative Humidity
(non-condensing)
10
90
%
Weight
TIU050
TIU10X
TIU11X
TIU20X
TIU10X
TIU11X
TIU20X
320
370
470
370
470
1870
350
400
500
400
500
1900
g
Dimensions
TIU050
TIU10X
TIU11X
TIU20X
TIU10X
TIU11X
TIU20X
179 x 111 x 60
121 x 105 x 38
172 x 105 x 38
282 x 194 x 62
121 x 105 x 38
172 x 105 x 38
282 x 194 x 62
mm
Cable Lengths
†
RS-232
RS-485
RS-485
1
15
1500
m
IP rating
NEMA 4-12/IP65
EMC Conformance
EN 55 022, Radiated and Conducted Emissions
EN 61000-4-3, Radiated and Conducted RF Immunity
ENV 50144
EN 61000-4-3, Radiated and Conducted RF Immunity
ENV 50144
†
Cables beyond the maximum recommended length may create communication problems. Both ends of
an RS-485 network must be properly terminated at 120
Ω
and grounded.