CH. 3: TIU100/101/102/103                             06 Apr 2000                                                         PAGE 21
GFK-1819
3.5.1 
TIU10X Configuration of the RS-485 Port
The configuration bank (shown in Figure 3.8) sets the parameters of the RS-485 port as described in
Table 3.1.
Table 3.1 – Configuration Bank
Switch 1
ON: Pull-up (must be used together with switch 3)
OFF: no Pull-up
Switch 2
ON: 120
Ω
 termination
OFF: no termination
Switch 3
ON: Pull-down (must be used together with switch 1)
OFF: no Pull-down
Switch 4
Reserved for future use
NOTE: Switch 1 and 3 must be used together.  Either both pull-up and pull-down are
used or neither is used.
Pull-up and Pull-down switches are used to increase the signal level on the RS-485 bus.  This is useful if
there is a long bus and a significant amount of attenuation is anticipated.