EXCEL 50/100/500/600/800 
ATTRIBUTES 
 
 
EN2B-0092GE51 R0512 
17 
In the datapoint description, the alarms can be influenced using the functions 
described below (see also Table 6 on page 17). 
 
 
Alarm type 
For each datapoint in the datapoint description, the user can determine whether the 
signals generated are to be treated as critical or non-critical alarm. 
 
 
Alarm delay 
An alarm signal can be delayed by entering an alarm delay time. An alarm signal 
will be generated only if an alarm continues uninterrupted during the alarm delay 
time. 
 
 
Suppress alarm 
If an alarm signal is not desired from a particular datapoint, this can be fixed in the 
datapoint description. Thus, all the alarm signals relevant to the particular datapoint 
and the "Operating Mode" alarm types are suppressed. 
 
 
 
Fig. 7. Alarm condition depending on point value and Suppress Alarm status 
Fig. 7 shows an example of a changing point value that rises above and falls below 
the limit Max 2. If Suppress Alarm is not active, then the alarm condition switches 
between normal to alarm, according to the limit Max 2. If Suppress Alarm is active, 
then the alarm condition remains normal unless Suppress Alarm is switched off 
before the point value falls below the limit Max 2. Regardless of the setting of the 
Alarm suppression flag, an alarm is entered into the controller's history buffer and is 
also available in the EBI alarm report. 
 
 
Point alarm 
It is possible to view all datapoints at the operator interfaces for which the limit 
value (analog point) or the alarm status (digital point) is currently exceeded. 
Driven by a menu, the user address and the accompanying alarm text are displayed 
on the XI581 (not with XCL5010, Excel 100C) or XI582 operator interfaces or Excel 
50 MMI. 
On the XL-Online operator interface, a datapoint within the framework of the 
datapoint description can be seen in all four password levels. If a current alarm is 
present for the point in question, the attribute “Point in Alarm” produces the display 
“Yes”, otherwise “No”. 
Within the framework of the datapoint description, it is possible, under the attribute 
“Alarm text”, to enter an alarm text of up to 18 characters in addition to the prepro-
grammed text. There are 256 alarm texts in total. 
Table 6 presents a summary of various alarm types and attributes. 
 
Table 6. Alarm summary 
alarm type/attributes  alarm status 
enter alarm 
delay time 
alarm 
suppression 
point in 
alarm 
no. of prepro-
grammed texts 
supplementary 
text 
Limit Values 
selection in DPD* 
possible 
possible 
possible 
Alarm Status 
selection in DPD* 
possible 
possible 
possible 
Maintenance Alarm 
selection in DPD* 
possible 
Totalizer 
selection in DPD* 
possible 
Operating Mode 
always critical 
possible 
System Alarms 
always critical 
approx. 110