Maintenance and Inspection
T
roub
leshooting
and Maintenance
6–14
Inverter Output Voltage Measurement Techniques
Taking voltage measurements around drives equipment requires the right equipment and 
a safe approach. You are working with high voltages and high-frequency switching 
waveforms that are not pure sinusoids. Digital voltmeters will not usually produce 
reliable readings for these waveforms. And, it is usually risky to connect high voltage 
signals to oscilloscopes. The inverter output semiconductors have some leakage, and
no-load measurements produce misleading results. So, we highly recommend using the 
following circuits to measure voltage for performing the equipment inspections.
HIGH VOLTAGE: Be careful not to touch wiring or connector terminals when working 
with the inverters and taking measurements. Be sure to place the measurement circuitry 
components above in an insulated housing before using them.
220 k
Ω
2W
+
220 k
Ω
2W
+
Voltage measurement with load
Inverter
Voltage measurement without load
Additional resistor
Inverter
5 k
Ω
30W
V Class
Diode Bridge
Voltmeter
200V Class
600V 0.01A min.
300V range
400V Class
100V 0.1A min.
600V range
V Class
Diode Bridge
Voltmeter
200V Class
600V 0.01A min.
300V range
400V Class
100V 0.1A min.
600V range
L1/R
L2/S
L3/T
U/T1
V/T2
W/T3
L1/R
L2/S
L3/T
U/T1
V/T2
W/T3