AEG 8000012364 BAL User Manual

Page of 42
"UniVert 2" inverter 
 
Page 23 of 42 
8000012364 BAL, en 
4.10 
CAN Bus Interfaces (X6, X7) 
The unit can be controlled and monitored via the 10-pin CAN bus 
connector X6, if the SBS is installed in a power supply cabinet with 
PSM control unit. 
The CAN bus connector X7 is always required for communication 
with the INV when operated with SBS. In this case, only the end of 
the bus on the INV must have a terminating resistor connected; a bus 
terminating resistor is integrated in the SBS! (See Figure 1.) 
 
4.11 DIL 
Switch 
An 8-pin DIL switch is located below the LCD. All settings of/ changes 
to the DIL switch are only activated at mains operation, i.e. when the 
operating status is "on". Also press the Reset button to take over the 
settings of the DIL switches. It is counted from the left S3.1 to the 
right S3.8, switches that are pushed in at the bottom signify "open"! 
The setting of the switches is shown on the display as a check 
whenever a change is made; 0 = open; 1 = closed. 
 
Switches S3.1, S3.2 and S3.3: Number of parallel INVs in the 
system 
The settings must be the same on all INVs and the SBS! 
Example: 4 INVs are in the system, at least 3 INVs should run, 
i.e. 1 INV is redundant: S3.1=0; S3.2=1; S3.3=1; S3.7=0; S3.8=1 
 
 
S3.1 S3.2 S3.3 
1 INV 
0 0 0 
2 INVs 
0 0 1 
3 INVs 
0 1 0 
4 INVs 
0 1 1 
5 INVs 
1 0 0 
6 INVs 
1 0 1 
7 INVs 
1 1 0 
8 INVs 
1 1 1