Type 
E-number 
E230 E230/115/2-VFp26,5-8 
3000000646 
Rated output capacity 
26.5 kVA 
Power loss 
< 200 W 
AC rated input voltage 
230 V 
AC rated input frequency 
50 Hz 
Monitoring systems 
 
AC mains undervoltage, 
blocking of the SBS 
Fault < 90% nominal (207 V), without delay 
Acknowledgement > 90% nominal (211 V) 
AC mains overvoltage, 
blocking of the SBS 
Fault > 110% nominal (253 V), without delay 
Acknowledgement < 110% nominal (248 V) 
AC load undervoltage, 
switchover to mains 
Fault < 88% nominal (202 V), without delay 
Acknowledgement > 88% nominal (207 V) 
AC load overvoltage, switchover 
to mains 
Fault > 112% nominal (258 V), without delay 
Acknowledgement < 112% nominal (253 V) 
Overtemperature, message 
Fault > 80
°C, acknowledgement < 70°C, 4 s delay 
self-acknowledging 
Synchronism 
INV / SBS circuit 
Fault phase deviation > 3° el., without delay 
Acknowledgement phase deviation < 2.9° el., 2 s delay