Applicable standards pertaining to switching surges 
 
Consult Table 2 for the standards applicable to VCB switching surges. 
 
Table 2 Applicable Standards Pertaining to Switching Surges 
 
Circuit 
breaker 
type 
 
Load type 
Rotating 
machine *
 
Dry type 
transformer 
(insulation 
resistance 
below 
class A) 
Oil-immersed 
transformer 
(insulation 
resistance 
class A) 
 
When there is 
electronic 
equipment on 
transformer 
low voltage 
side 
Phase advance 
capacitor *
4, 
*
 
Ordinary 
Protected by CR 
suppressor *
 
Protected by 
surge 
suppressor 
 
No special 
restrictions 
Protected by CR 
suppressor *
 
6.6 kV circuit: 
No special 
restrictions 
up to 300 kVA 
Low surge 
type 
 
No special 
restrictions *
 
No special 
restrictions *
 
No special 
restrictions 
Protected by CR 
suppressor *
 
6.6 kV circuit: 
No special 
restrictions 
up to 4000 kVA 
*1. Mainly induction motors, but also includes synchronizing generators for private generator 
equipment. 
*2. Use a CR suppressor for surge protection when inching at 55 kW (75HP) or below and on 
   inductance regulators. 
*3. Use an arrester for surge protection on circuits that require cutting off of excitation rush current. 
*4. When the capacity of the group of capacitors exceeds 300 kVA, insert a series reactor (6%). 
*5. For high-frequencies included in the applicable circuit, use 135% or below of the fifth harmonic 
as established in the standards for phase advance capacitors (JIS C 4801). 
*6. Table 3 shows the models of applicable CR suppressor. 
 
Table 3 CR Suppressors 
 
Circuit voltage 
CR suppressor model 
6.6 kV 
NV60K304T1 
(three-phase)