Toshiba HV6CS-MU Installation Instruction

Page of 38
 
 
- 14 - 
 
 
 
 
 
 
 
 
 
 
 
 
    Table 
Tightening 
Torque 
 
 
 
 
 
 
 
 
 
 
 
3.1.2 Mounting Directly onto the Floor 
The VCB should be mounted to a surface with a levelness of ±0.5 mm. If there are any large 
gaps, use spacers to adjust. Check to make sure that the VCB is in OPEN status, and then       
mount it using the steps shown in Figures 10 and 11 in that order. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Screw 
nominal 
dia. 
Tightening 
torque 
Screw 
nominal 
dia. 
Tightening torque 
M4 
1.47 to 1.96 N-m 
(15 to 20 kgf-cm) 
M8 
11.8 to 14.7 N-m 
(120 to 150 kgf-cm) 
M5 
2.94 to 3.92 N-m 
(30 to 40 kgf-cm) 
M10 
24.5 to 30.9 N-m 
(250 to 315 kgf-cm) 
M6 
4.90 to 6.37 N-m 
(50 to 65 kgf-cm) 
M12 
44.1 to 55.4 N-m 
(450 to 565 kgf-cm) 
Figure 10 Fasten the VCB onto an angle or a flat plate. The 
use of M8 hexagonal bolts (either 50 mm or 35 mm) is 
recommended. The tightening torque should be 11.8 to 14.7 
N · m (120 to 150 kgf · cm).
 
Figure 11 Either mounting 
method may be used.
 
Figure 9 Fix the front plate onto panel 
with two (2) M8 bolts and two (2) M4 
screws removed at step shown in Fig. 8.
 
 
ANGLE 
PANEL