Hearth & Home Technologies   •  BE-36-C, BE-36-CIPI  •  397-981 Rev. V  1/07
14
E.  Vent Diagrams
Fire Risk.   Explosion Risk.
Do NOT pack insulation or other combustibles between ceiling fi restops.
•  ALWAYS maintain specifi ed clearances around venting and fi restop systems.
•  Install wall shield and ceiling fi restops as specifi ed.
Failure to keep insulation or other material away from vent pipe may cause fi re.
WARNING
NOTE: There MUST be a 25% 
reduction in total H when using 
fl ex vent except when using the 
simple up and out installation 
(see Figure 5.3).
Note: Use SL D- Series 
components only.
V Minimum
H
Maximum
BE-36-C NG
BE-36-C LP
90 Elbow Only
1-1/2 ft.
457 mm
1-1/2 ft.
457 mm
1/2 ft.
152 mm
2 ft.
610 mm
1-1/2 ft.
457 mm
1-1/2 ft. 457 mm
3 ft.
914 mm
3 ft.
914 mm
2-1/2 ft. 762 mm
5 ft.
1.5 m
5 ft.
1.5 m
3-1/2 ft.
1.1 m
7 ft.
2.1 m
7 ft.
2.1 m
4-1/2 ft.
1.4 m
15 ft.
4.6 m
15 ft.
4.6 m
H
1
 MAX. =15 FT (4.6 m)
V
1
 + H
1
 MAX. = 40 FT (12.2 m)
NOTE: There MUST be a 25% 
reduction in total H when using 
fl ex vent except when using the 
simple up and out installation 
(see Figure 5.3).
Note: Use SL D- Series 
components only.
H
2
H
1
V
1
Figure 5.4
Figure 5.5
1.   Top Vent - Horizontal Termination
One Elbow
Two Elbows
H
1
V
1
V Minimum
H
+ H
Maximum
BE-36-C NG
BE-36-C LP
90 Elbow Only
1/2 ft.
152 mm
1/2 ft.
152 mm
1/2 ft.
152 mm
1 ft.
305 mm
1/2 ft.
152 mm
1-1/2 ft. 457 mm
2 ft.
610 mm
2 ft.
610 mm
2-1/2 ft. 762 mm
4 ft.
1.2 m
4 ft.
1.2 m
3-1/2 ft.
1.1 m
6 ft.
1.8 m
6 ft.
1.8 m
4-1/2 ft.
1.4 m
14 ft.
4.3 m
14 ft.
4.3 m
H
1
 + H
2
 MAX. =14 FT (4.3 m)
V
1
 + H
1
 + H
2
 MAX. = 40 FT (12.2 m)