B.  Disassembly of Vent Sections 
     
(DVP Pipe ONLY)
Improper support may allow vent to sag or separate.
Securing the Vent Sections
Vertical Sections
Vertical sections of pipe must be supported every 8 feet 
after the 25 foot maximum unsupported rise. The vent sup-
port or plumber’s strap (spaced 120° apart) may be used 
to do this (see Figure 8.8).
 Horizontal Sections
Horizontal sections of vent must be supported every 5 feet 
with a vent support or plumber’s strap.
Figure 8.8  Securing Vertical Pipe Sections
To disassemble any two pieces of pipe, rotate either section 
(see Figure 8.10), so that the seams on both pipe sections 
are aligned (see Figure 8.11). They can then be carefully 
pulled apart.
Figure 8.11   Align and Disassemble Vent Sections
Figure 8.10  Rotate Seams for Disassembly
Figure 8.9  Securing Horizontal Pipe Sections
Fire Risk.
Explosion Risk.
Combustion Fume Risk.
Use vent run supports per installation 
instructions. 
Connect vent sections per installation 
instructions.
•  Maintain all clearances to combustibles.  
•  Do NOT allow vent  to sag below 
connection point to appliance.
WARNING