Vinotemp WM250-850SCU User Manual

Page of 8
VINO2500SSD, 4500SSD 
VINO6500SSD, 8500SSD 
 
Installer’s Instruction 
 
Federal law requires that WINE-MATE split cooling systems be 
installed by an EPA certified refrigeration technician. 
 
WINE-MATE split system is shipped as components and is ready for use only 
after a certified refrigeration technician has properly installed, chatged and tested 
the system. Proper installation is critical. Vinotemp can only warrant the quality of 
the components. The installation and proper operation of the system must be 
warranted by the installer. Installation of the system must be done in accordance 
with all state and local building codes.  
The condensing unit and evaporator unit are connected by a liquid line and an 
insulated suction line that are supplied by the installer. These lines must be 
properly sized for the distance between the two units. After the units and the lines 
are installed, the system must be pressure tested. If no leaks are found, 
evacuate and charge system with R134A. Refrigerant amount will vary 
depending on the length of line set. 
 
1. Condensing Unit 
 
•  Place the condensing units WM250-850SCU in a properly ventilated 
location. If it is not, heat exhausted by the condensing unit will build up 
and the cooling system will not operate properly.  
•  Leave minimum 5 feet clearance for the exhaust side and leave minimum 
1 foot clearance for the fresh air intake side. 
•  Condensing unit shall be elevated to avoid possible flooding and shaded 
from direct sun. It shall not be exposed to temperatures higher than 110 
°
F or lower than 45 
°
F (optional low ambient kit for 20 
°
F). 
  
2. Evaporator Unit