WATER FLOW REQUIREMENT FOR COPELAND WATER COOLED CONDENSING UNITS
 *
Gallons per hour per 1,000 BTU/hr (Net)
Temperature Difference, Entering Water to Condensing
20
°
F T.D.
30
°
F T.D.
Operating
Conditions
Series
Parallel
Series
Parallel
Water Flow
Water Flow
Water Flow
Water Flow
90
°
F Condensing
45
°
F Evap.
8.1
10.1
5.5
6.8
15
°
F Evap.
8.9
11.1
6.0
7.5
-10
°
F Evap.
10.0
12.5
6.8
8.5
100
°
F Condensing
45
°
F Evap.
8.2
10.3
5.6
6.9
15
°
F Evap.
9.2
11.5
6.2
7.8
-10
°
F Evap.
10.4
13.0
7.1
8.8
110
°
F Condensing
45
°
F Evap.
8.5
10.5
5.7
7.1
15
°
F Evap.
9.5
11.8
6.4
8.0
-10
°
F Evap.
10.9
13.5
7.4
9.2