Heatcraft Refrigeration Products H-IM-79E User Manual

Page of 36
15
Programming & Reviewing
Locking The Beacon II Board
The Beacon II board is lockable to prevent programmed 
setting changes by unauthorized personnel. When 
locked, the program setpoints cannot be changed.
To 
lock the setting:
 
• 
Press “
PROGRAM REVIEW” button.
 
• 
Press and 
hold “MONITOR” button.
 
• 
While holding “MONITOR” button, 
 
 
press “
ENTER” button.
 
• 
The LCD will display 
Loc.
This will prevent unauthorized personnel program 
changes. To 
unlock, repeat steps above. LCD will 
display “
UnL”.
•  OFF 
Box Temp
/ oFF  Box Temperature/ Mode is displayed
 
  All Evaporators 
 
 
•  COOLING
 
  Single Evaporator-   Box Temp
/Coo  Box Temperature/ Mode is displayed
 
  Multiple Evaporators   
 
 
     Master Evap
-
Box Temp
/ Coo  Box Temperature/ Mode is displayed
 
     Slave Evaps - 
Coo  
Operating Mode is displayed
•  Pumpdown
 
  All Evaporators 
Pdn
•  DEFROST
 
  All Evaporators 
dEF
 
•  TEST
 
  All Evaporators 
tSt
•  SERVICE
 
  All Evaporators 
SEr
•  ALARMS  
A 1 
 
High Box Temp
 
A 2 
 
Low Box temp
 
A 3
 System Start-up failure
 
   
 
 
 
Compressor pumps down and tries  
 
   
 
 
 
to restart after 4 minutes.
 
A 4 
 
Input Fault
 
   
 
 
 
Box Temp., Suction Temp., Pressure
 
   
 
 
 
Transducer open or not installed
STATUS INDICATOR LED
A RED, three-digit , alphanumeric LED on the 
Beacon II board  indicates status, alarms and  
error codes. 
Programming And Reviewing
Settings/Changes (Cont’d.)
Use this button to 
“CLEAR/TEST”
Pressing this button ONCE
will return the LED display to 
the default display. With the system in the 
OFF mode, 
pressing and holding this button will start the 
“TEST” 
mode. In the “
TEST” mode it will cycle through each 
output for 10 seconds. The display will only show “tst” 
during “
TEST” mode. Test mode will automatically 
terminate after 3 sequences.