Heatcraft Refrigeration Products H-IM-79E User Manual

Page of 36
20
Checking Operation Of Expansion
Valve (EEV)
To check if the expansion valve is closing properly: 
 
Install a pressure gauge-set to suction line at  
 
the condensing unit. With the system running,  
 
close the valve on the liquid line, at the con 
 
densing unit. The system should pumpdown  
 
and shut off on the Low Pressure switch (LPS).  
 
If the system does not pumpdown and trip on  
 
the LPS then the compressor valves are weak  
 
and needs to be changed.
 
After the system pumps-down and trip on the  
 
LPS, put the system in the service mode. This  
 
will cause the Expansion valve to close. Open  
 
the valve on the liquid line, at the condensing  
 
unit. The suction pressure reading on the gauge  
 
set should not increase. If the suction pressure  
 
increases then the expansion valve is leaking  
 
and should be changed.
Checking Operation of Expansion Valve
If the expansion valve is suspected of not functioning 
properly the motor windings resistance should be 
measured. This is a bipolar motor with two windings. 
Measure the resistance at the pins, on top of the valve, 
between locations A and B  
or C and D.  
Expansion Valve
Motor Winding
Pins
The Expansion valve position can be monitored from 
the LED display pressing the “
MONITOR” button and 
scrolling to 
ESP. This will indicate the number of steps 
the valve is open.
This can also be checked by using the EXV test pins on 
the board. This is indicated by a 0 to 5 Volts DC signal. 
At 0 Volt the valve is closed and at 5 Volts the valve is 
fully open. At values between 0 and 5 Volt, the valve will 
be opened proportionately.
Use the “
MONITOR” button to display “SCP”” 
Evaporator Suction Pressure. Record the pressure 
displayed. Start the system and observe the pressure 
displayed. If the pressure does not increase, the 
expansion valve could be defective. 
If the system is running, use the “
MONITOR” button to 
display “
SCP” Evaporator Suction Pressure. Record the 
pressure displayed. While the system is running, press 
the “
FORCE SERVICE” button. Observe the pressure 
while the system is pumping down. The pressure should 
decrease. If it does not, this indicates a defective valve.
Expansion Valve Motor Winding Resistance
   
A•   •C
                
   •           •
   B         D
(Note that the pins are not labeled A, B, C, D. This 
labeling is just for reference. Also, two of the pins, at 
location B and location D, have a wider spacing between 
them than between location A and C) 
For valve size 29320003 and 2930004, the resistance 
measured between pin locations A and B or C and D 
should be approximately 336 Ohms when valve is at 
75ºF.
For valve size 2930007, 29320008, 29320013 and 
29320014, the resistance measured between pin 
locations A and B or C and D should be approximately 
116 Ohms when the valve is at 75ºF.
Continues to Page 21