Heatcraft Refrigeration Products H-IM-79E User Manual

Page of 36
4
Installation Tips
 
 
•  Use a minimum 18 gauge wire for all low  
 
 
voltage connections
 
 
•  The Beacon II board gets its 24 VAC power  
 
 
supply from a transformer mounted in the  
 
 
electrical end of each evaporator. On  
 
 
208-240 volt systems the multi-tap  
 
 
transformer is shipped from our factory wired 
 
 
for 240 volts. If your supply voltage is 208  
 
 
volt you must change to the 208 volt tap on 
 
 
the transformer.
 
 
 
 
NOTE: On multiple evaporators, since a 
 
 
 
transformer is in each evaporator, the  
 
 
 
voltage tap must be set on each  
 
 
 
evaporator. 
 
•  Refer to wiring schematic shipped on units  
 
 
for unit wiring. Schematics in this Installation 
 
 
& Operation Manual are typical wiring  
 
 
schematics only. 
 
•  Program ALL slave evaporators as SLAVES. 
 
 
•  Evaporators are shipped from our factory  
 
 
with a preset box setpoint temperature of  
 
 
35°F for air defrost and -10°F for electric  
 
 
defrost. If your box setpoint temperature  
 
 
requirements are different this must be set  
 
 
using directions outlined under “Room  
 
 
Temperature Control”. 
 
•    The suction line temperature sensor MUST  
 
 
be removed from the suction line before  
 
 
brazing the suction tubing. The sensor  
 
 
MUST then be reinstalled on the suction  
 
 
line after brazing is completed and the tubing  
 
 
has cooled. Insulate when finished. 
 
•    The low pressure switch time delay relay, 
 
 
located in the condensing unit, must be set  
 
 
to 1 minute. 
 
•    If electrical power will be connected prior to  
 
 
evacuation and charging of system, unplug  
 
 
electric expansion valve from board until  
 
 
system is ready to be evacuated, leak tested  
 
 
and charged.
Installation
 
•   Some systems may require the crankcase  
 
 
heater be energized 24 hours prior to  
 
 
start-up. The Beacon should be de- 
 
 
energized for this period by placing it in  
 
 
the 
SERVICE MODE. This is done by 
 
 
pressing the 
FORCE SERVICE button 
 
 
twice. To start the system cooling, press the  
 
 
CLEAR button. 
 
•    Room sensors must be left connected on  
 
 
ALL evaporators. 
 
•    A pressure transducer is installed on the  
 
 
evaporator. Do not leak test system above  
 
 
150 PSI or damage to transducer could  
 
 
occur. If leak testing must be greater than 
 
 
150 psig, disconnect the transducer from  
 
 
he suction header and reconnect after  
 
 
testing is complete.
 
Condensing Unit
 
The condensing unit control panel contains the relays, 
contactors, time delay and a terminal block which is 
appropriately marked to match the low voltage wiring 
connections. A sensor for outdoor air temperature 
measurement is installed on the condensing unit.
Condensing unit must be installed using proper 
refrigeration practices and codes. Make sure there is 
sufficient clearances around unit for adequate air flow 
and access.
Evaporator Unit
The evaporator contains the Beacon II controller, electric 
expansion valve, pressure transducer, distributor, orifice, 
transformer and three sensors. These components are 
all factory mounted and wired. The three sensors are 
factory mounted and provide input to the controller from 
the following: defrost temp., suction temp., room temp.
Each evaporator unit must be installed using proper 
refrigeration practices and codes. Make sure the 
piping is correctly sized and properly routed. It is highly 
recommended that the liquid and suction lines be 
insulated. There must also be good clearance around 
unit. See Heatcraft Refrigeration Installation & Operation 
Manual for more details.