TrueFRESH™ ERV/HRV Ventilation Systems   69-2480EF—05
16
Installation Steps (continued)
5
Installing the condensation drain line
Insert the threaded drain adapter through the bottom of
the unit and hand tighten the plastic nut supplied with 
the drain kit. 
Use a wrench to tighten the nut another half turn to  
ensure a complete seal. 
Install the condensate tubing by pushing the clear
plastic tubing over the drain adapter.
Make a condensate trap by looping the clear plastic
tubing. This loop will prevent foul odors from entering
the unit.
Use a condensate pump if you don’t have access to  
the floor drain.
Drainless Application
NOTE:   If installing an ERV unit (VNT5150E1000 or VNT5200E1000) in a region where the outdoor 
temperature does not drop below freezing, the condensate drain line does not need to be
installed and the unit may be installed as a drainless application.
1. Insert the threaded drain adapter through the bottom  
  of the ERV with the drain connection inside of the unit  
 as shown in the figure.
2. Fit the rubber washer over the drain adapter and then 
  attach the plastic nut.
3. Hand tighten the plastic nut supplied with the drain kit.
4. Use a wrench to tighten the nut another half turn to  
  ensure a complete seal.
5. Attach the drain cap to the drain adapter inside the  
 unit.