Balancing Reset
Checkout
TrueFRESH™ ERV/HRV Ventilation Systems   69-2480EF—05
26
•  Apply power to the unit. Move the selector switch to the CONT position to verify that the unit turns on in 
continuous speed.  
•  Initiate a ventilation call from each of the external controls. Verify that the ERV/HRV unit turns on in high 
speed. 
•  Return the selector switch to the desired position and the external controls to the desired settings. 
•  Inspect the ducting to ensure that there are no kinks and correct as necessary.
LED
3-POSITION
SELECTOR SWITCH
SPEED CONTROL
BUTTONS (+ AND -)
Speed
Control
Open for 
Instructions
M32371
NOTE:  Once balancing is completed, balancing cannot be changed without resetting the unit.
To reset:
1. Press the (+) and (–) buttons simultaneously for 10 seconds.
2. Indicator light will turn yellow at 5 seconds. 
3. Indicator light will turn green at 10 seconds. 
4. Release both buttons.
5. Unit has been reset and can be put into balancing mode again.