APC 1400 User Manual

Page of 66
15
English
11.2 Extended storage
During extended storage in environments where the ambient temperature is –15 to +30 °C
(+5 to +86 °F),  charge  the  UPS’s  battery  every  6 months
During extended storage in environments where the ambient temperature is +30 to +45 °C
(+86 to +113 °F),  charge  the  UPS’s  battery  every  3 months.
12. Specifications
420 VA
650 VA
1000 VA
1400 VA
Acceptable input voltage
0 - 160 VAC
Input voltage (on-line operation)
92-150 VAC
Output voltage
103-132 VAC
Nominal input frequency
50 or 60 Hz, autosensing
Input Protection
Resettable circuit breaker
Frequency limits (on-line operation)
50 or 60 Hz, ±5%
Transfer time
2 ms typical, 4 ms maximum
Maximum load
420 VA 280 W 650 VA 400 W 1000 VA 670 W 1400 VA 950 W
On-battery output voltage
115 VAC
On-battery frequency
50 or 60 Hz, ±0.1 Hz; unless synchronized to utility during brownout.
On-battery waveshape
Stepped sine-wave
Trapezoid
Protection
Overcurrent and short-circuit protected, latching shutdown on overload.
Surge energy rating (one time,
10/1000 µs waveform)
320 J
480 J
Surge current capability (one time,
8/20 µs waveform)
6500 A maximum
Surge response time
0 ns (instantaneous) normal mode;
<5 ns common mode
Surge voltage let-through (percentage
of applied ANSI C62.41 Cat. A ±6
kV test waveform)
0.7%
0.3%
Noise Filter
Normal and common mode EMI/RFI suppression,
100 kHz to 10 MHz
Battery type
Spill proof, maintenance free, user replaceable, sealed lead-acid
Typical battery life
3 to 6 years, depending on number of discharge cycles and ambient
temperature
Typical recharge time
2 to 5 hours from total discharge