2.3. T
ECHNICAL SPECIFICATIONS
Standards
Construction and safety : 
IEC-60439-1
Conception : 
IEC-60289, IEC-60727
IP rating
Unprotected :
IP00
Protected :
IP21
Electrical specifications
Frequency :
50 / 60Hz
Nominal voltage between phases :
400V +15% / -10%
Reduction ratio  
I
I
Neutral upstream
Neutral downstream
 1:10
Ratio   
I
I
Neutral
Phase
 :
≤ 1.8
Inrush current :
≤ I
nominal
Overload capacity :
10% - 1 hour
25% - 10 minutes
50% - 2 minutes
Insulation class :
1.1 kV
Dielectric strength :
3 kV
Thermal class of insulation:
H
Environmental conditions
Maximum ambient temperature :
50°C
Maximum altitude :
1000m
Maximum relative humidity :
90% without condensation
Please contact your MGE UPS SYSTEMS correspondent for different operating conditions.
→ 