APC 9000 User Manual
34006452EN/AC
- Page 30
Shutdown
Modular UPS with external maintenance bypass
Frequency converters
(no Mains 2)
– shutdown each UPS (see section "shutdown of
a unit");
a unit");
– transfer to the maintenance bypass in the order
indicated below (the load is supplied directly by
Mains 2 via bypass
Mains 2 via bypass
switch Q3BP):
– in the maintenance bypass cubicle, close
switch Q3BP, then open switch Q5N;
switch Q3BP, then open switch Q5N;
– open output switch Q5N for each UPS;
– cut the Mains 2 supply to each UPS by opening
the upstream protection devices;
the upstream protection devices;
– open battery circuit breaker QF1 on each UPS;
– open input switch Q1 on each UPS;
– the UPSs are de-energised once the capacitors
– the UPSs are de-energised once the capacitors
have discharged.
Multi-bypass modular UPS
– shutdown each UPS (see section "shutdown of
a unit");
– the load is supplied via the Mains 2 of each
UPS;
UPS;
– close switch Q3BP on each UPS, the load is
supplied by the Mains 2, via the bypass lines
(Q3BP) of each UPS;
(Q3BP) of each UPS;
– open switches Q5N, Q4S, Q1 and QF1 on each
UPS, the situation is that shown in the figure
opposite;
opposite;
– the UPSs are de-energised once the capacitors
have discharged.
Shutdown of the inverters results in the interruption of the load;
– shut down each inverter (see the "shutdown of a unit" section);
– open battery circuit breaker QF1 and Mains 1 input switch Q1 on each unit;
– open battery circuit breaker QF1 and Mains 1 input switch Q1 on each unit;
– the system is powered down (except the Mains 1 cables upstream from switch Q1). A full powering down requires the
opening of the upstream protection device on Mains 1.
opening of the upstream protection device on Mains 1.
Q1
Q5N
QF1
Q3BP
Q4S
Q1
Q5N
QF1
Q4S
Modular UPS 2
Modular UPS 1
Q5N
External maintenance bypass
load
battery
inverter
mains 1
rectifier-
charger
static switch
mains 2
battery
inverter
mains 1
rectifier-
charger
static switch
mains 2
Q1
Q5N
QF1
Q3BP
Q4S
Q1
Q5N
QF1
Q3BP
Q4S
Modular UPS 2
Modular UPS 1
load
battery
inverter
mains 1
rectifier-
charger
static switch
battery
inverter
mains 1
rectifier-
charger
static switch
mains 2
Q1
Q5N
ON OFF
(I)
(0)
ON
(I)
QF1
OFF
ON
(0)
(I)