Shutdown
Modular UPS with external maintenance bypass  
 Frequency converters 
(no Mains 2)
 
– shutdown each UPS (see section "shutdown of 
a unit");
– transfer to the maintenance bypass in the order 
indicated below (the load is supplied directly by 
Mains 2 via bypass 
switch Q3BP):
– in the maintenance bypass cubicle, close 
switch Q3BP, then open switch Q5N;
– open output switch Q5N for each UPS;
– cut the Mains 2 supply to each UPS by opening 
the upstream protection devices;
– open battery circuit breaker QF1 on each UPS;
– open input switch Q1 on each UPS;
– the UPSs are de-energised once the capacitors 
have discharged.
Multi-bypass modular UPS  
– shutdown each UPS (see section "shutdown of 
a unit");
– the load is supplied via the Mains 2 of each 
UPS;
– close switch Q3BP on each UPS, the load is 
supplied by the Mains 2, via the bypass lines 
(Q3BP) of each UPS;
– open switches Q5N, Q4S, Q1 and QF1 on each 
UPS, the situation is that shown in the figure 
opposite;
– the UPSs are de-energised once the capacitors 
have discharged.
Shutdown of the inverters results in the interruption of the load;
– shut down each inverter (see the "shutdown of a unit" section);
– open battery circuit breaker QF1 and Mains 1 input switch Q1 on each unit;
– the system is powered down (except the Mains 1 cables upstream from switch Q1). A full powering down requires the 
opening of the upstream protection device on Mains 1.
Q1
Q5N
QF1
Q3BP
Q4S
Q1
Q5N
QF1
Q4S
Modular UPS 2
Modular UPS 1
Q5N
External maintenance bypass
load
battery
inverter
mains 1
rectifier-
charger
static switch
mains 2
battery
inverter
mains 1
rectifier-
charger
static switch
mains 2
Q1
Q5N
QF1
Q3BP
Q4S
Q1
Q5N
QF1
Q3BP
Q4S
Modular UPS 2
Modular UPS 1
load
battery
inverter
mains 1
rectifier-
charger
static switch
battery
inverter
mains 1
rectifier-
charger
static switch
mains 2
Q1
Q5N
ON OFF
(I)
(0)
ON
(I)
QF1
OFF
ON
(0)
(I)