MGE UPS Systems 12 kVA User Manual

Page of 32
 
51033212EN/AC
 - Page 27
1. Secure the connection module       using the two screws      .
2. Reconnect the connection cable(s) to the battery module(s).
3. Switch the battery circuit breaker(s)       to the ON position
and check that LED       is ON.
Check that UPS personalization settings still
correspond to the equipment to be supplied
(see section 3.5).
4. Press button       and wait 20 seconds.
5. Check that LED        is ON.
If LED       is not ON, do not switch the manual
bypass to the intermediate position and call the
after-sales support department.
6. Turn the manual bypass switch       from the BYPASS position
to the intermediate position and check that LED       is OFF.
7. Turn the manual bypass switch       from the intermediate
position to the NORMAL position. 
LED        goes OFF and LED
goes ON.
The connected equipment is again protected by the UPS.