MGE UPS Systems Uninterruptible Power Provider User Manual

Page of 4
Pulsar Evolution UPS 
500
800
1100
1500
2200
3000/3000XL
Power VA/W
500/350
800/560
1100/700
1500/1000
2200/1540
3000/2000
Versions
1U Rack
Mini-Tower and 1U Rack
Versatile Tower/2U Rack
Installation possibilities
Rackable, stackable,
Mini-Tower version: vertical or horizontal
Rackable, stackable 
vertical tower                            
Rack version: rackable or stackable
or vertical tower with support base
or wall-mount
Number of outlets
4
4
4
4
6
6
Including Powershare outlets
2
2
2
2
2
2
Battery extension (EXB modules)
From 1 to 3 EXBs (1 to 12 for 3000XL)
Performances
Technology
High-Frequency Line-Interactive
Automatic voltage regulation
Booster/Fader
Output voltage waveform
Sinewave
Input voltage tolerances
92V/138V, adjustable to 80V/153V via supplied UPS-Driver software
Frequency
50/60 Hz, auto-select 
Output voltage on battery power
120VAC (adjustable to 100/120/127V via supplied UPS-Driver software)
Features
Automatic battery test
Weekly (interval adjustable via supplied UPS-Driver software)
Hot swappable batteries
x
x
x
x
x
x
Cold start
x
x
x
x
x
x
Deep discharge protection
x
x
x
x
x
x
UPS-Driver for Windows
Settings: Input voltage tolerances, Sensitivity, Battery test, ON/OFF conditions
Data line protection
Surge protection for RJ45 network connection
Network Administration/Monitoring
Communications
1 USB port + 1 Serial port
Software supplied (Solution-Pac CD)
Including local power management software and SNMP proxy-agents for Windows 2000/NT/98
Linux, Netware, OpenServer, Unixware, SUN Solaris, IBM AIX, HP UX, Compaq Tru64, etc.
Web-based monitoring
XML-@gent (October 2001)
Spare slots
1 slot for optional SNMP or status indication card 
Remote indications
Optional UPScontrol remote display
Standards/Warranty
Safety
EN 50091-1-1/EN60950(RD),IEC 60950,TÜV GS-Mark
Electromagnetic compatibility
EN 50091-2,EN 50022/B,IEC 62040-2,IEC 61000-3-2,IEC 61000-3-3
Design, production and services
ISO 9001
Marking
UL, cUL, FCC Class A, UL1778
Warranty (U.S. and Canada)
2 years, parts and labor
Dimensions, weight and ref.
500
800
1100
1500
2200
3000/3000XL
Tower dimensions (HxWxD in inches)
5.9 x 9.3 x 16.3
5.9 x 9.3 x 19.0
Rack dimensions (HxWxD in inches)
1.73 (1U) x 17.2 x 13.9
1.73 (1U) x 17.2 x 19.6
1.73 (1U) x 17.2 x 20.6
3.5 (2U) x 17.2 x 25.2
Tower/Rack weights (in =lbs.)
– / 19.8
23.1/34.1
25.3/35.2
33/41.9
74.7
80.4
EXB module weight
92.3
Accessories supplied
removable and repositionable 19” rack-mount brackets, universal telescopic rails,
with Rack versions:
mounting hardware kit, rear attachment, cable lock system
Tower ref.
89341
89343
89345
Rack ref.
89340
89342
89344
89346
Tower convertible to Rack ref.
89347
89348/89349
EXB module ref.
89350
MGE 
UPS 
SYSTEMS                                                    
T H E   U N I N T E R R U P T I B L E   P O W E R   P R O V I D E R
Characteristics
Battery charge level
Group of 6 outlets for 
equipment connection with 
2 programmable outlets
Power consumption
Complete user interface:
- on AC input / on battery 
- booster/fader mode 
- programmable outlet status 
- battery replacement required
or UPS fault
Connection
of additional
battery modules
Slot for optional
communications
card
Data line
protection
Automatic recognition
of battery extensions
RS232 communications
port
USB communications
port
Repositionable
logo and battery
access plate
Pulsar
Evolution
3000
evolution 101 2.02.QXD.pdf  3/5/02 2:14 AM  Page 4
 
13540 N FLORIDA AVE. 
SUITE 105 
TAMPA    FL 33613 
O M N I C O N T R O L S , I N C .
Phone : 
813-960-3445
 
FAX  813-960-4779 
www.omnicontrols.com