MGE UPS Systems FlexPDU 8 DIN User Manual

Page of 12
3400803900/AC 
140, Avenue Jean Kuntzmann
ZIRST - Montbonnot St Martin
38334 - Saint Ismier Cedex - France
www.mgeups.com
MGE UPS SYSTEMS
T  H  E    U  N  I  N  T  E  R  R  U  P  T  I  B  L  E    P  O  W  E  R    P  R  O  V  I  D  E  R
Technical characteristics
FlexPDU models : 8 FR, 8 DIN, 6 BS, 12 IEC, 6 UNI, 6 AUS  
Input
IEC 320 C20 16A 
Output
FlexPDU 8 FR :
FlexPDU 8 DIN :
FlexPDU 6 BS :
FlexPDU 12 IEC :
FlexPDU 6 UNI :
FlexPDU 6 AUS :
8 USE 16A socket-outlets + 1 IEC 320 C19 16 A
8 DIN 16A socket-outlets + 1 IEC 320 C19 16 A
2 x 3 BS 13A socket-outlets + 1 IEC 320 C19 16 A
2 x 6 IEC 320 C13 10A + 1 IEC 320 C19 16 A
6 UNI socket-outlets + 1 IEC 320 C19 16 A
6 AUS socket-outlets + 1 IEC 320 C19 16 A
Dimensions
 (HxLxD)
FlexPDU 8 FR / 8 DIN / 12 IEC / 6 AUS :
FlexPDU 6 BS / 6 UNI :
4.4 cm x 19 inches x 8 cm
5.2 cm x 19 inches x 12 cm
Performances
Nominal voltage
Frequency
Input nominal current
Maximal power
200/208/220/230/240 V
50/60 Hz
16 A
3680 VA
Standards
Product
FlexPDU 8 FR :
FlexPDU 8 DIN :
FlexPDU 6 BS :
FlexPDU 12 IEC :
FlexPDU 6 UNI :
FlexPDU 6 AUS :
IEC60884-1
DIN 49440-1, DIN 49440-5, DIN49440-6
BS 1363
IEC 60320-1, EN 60320-1
IEC 62040-1, IEC69050, IEC 60884-1-1
NZS/AS 3112
Marking
CE
Environment
Temperature
Humidity
Altitude
Storage -25°C to 55°C, operation 0°C to 45°C
Storage 10% to 90%, operation 20% to 90%
Transportation up to 12000 m, operation up to 1500 m