MGE UPS Systems 3000 RT 2U User Manual

Page of 24
34007776EN/AB
 - Page 19
5. Maintenance
Troubleshooting a UPS equipped with the HotSwap MBP module
  
5.2 Battery-module replacement
Safety recommendations 
The battery can cause electrocution and high short-circuit currents. The following safety cautions are required 
before servicing the battery components:
 Remove watches, rings, bracelets and all other metal objects from the hands and arms,
 Use tools with an insulated handle.
Battery-module removal
  
  
Indication
Diagnostic
Correction
 
10
The load is no longer supplied when 
the rotary switch (49) on the HotSwap 
MBP
 module is set to the Bypass 
position.
  The protected devices are 
connected to the UPS output 
instead of to the HotSwap MBP 
module.
  The AC-power cord is connected 
to the UPS input instead of to the 
HotSwap MBP module.
Check the wiring between the UPS 
and the HotSwap MBP module (see 
section 2.6).
11
The load is no longer supplied when 
the rotary switch (49) on the HotSwap 
MBP
 module is set to the Normal 
position.
  The UPS is shut down.
  The wiring between the UPS and 
the HotSwap MBP module is not 
correct.
  Start the UPS.
  Check the wiring between the UPS 
and the HotSwap MBP module (see 
section 2.6).
12
The load is no longer supplied if AC-
power fails.
  The rotary switch (49) on the 
HotSwap MBP module is set to the 
Bypass position.
  The wiring between the UPS and 
the HotSwap MBP module is not 
correct.
  Set the rotary switch (49) on the 
HotSwap MBP module to the 
Normal position.
  Check the wiring between the UPS 
and the HotSwap MBP module (see 
section 2.6).
If a fault leads to UPS shutdown, press the ON/OFF button (27) to clear the fault.
  
 
- Unscrew the left-hand side of the front 
panel (two screws).
- Remove the part.
  
 
C - Disconnect the battery block by 
separating the two connectors (never pull on 
the wires).
B
A
C