Hitachi L100 User Manual

Page of 192
Using Intelligent Output Terminals
Oper
ations
and Monitor
ing
4–22
Run Signal
When the [RUN] signal is selected as an 
intelligent output terminal, the inverter 
outputs a signal on that terminal when it is in 
Run Mode. The output logic is active low, and 
is the open collector type (switch to ground).
 
NOTE: The example circuit in the table above drives a relay coil. Note the use of a 
diode to prevent the negative-going turn-off spike generated by the coil from damaging 
the inverter’s output transistor.
[FW], 
[RV]
Output
freq.
Run 
Signal
start freq.
B 82
t
ON
1
0
1
0
Option
Code
Terminal 
Symbol
Function Name
Output 
State
Description
00
RUN
Run Signal
ON
when inverter is in Run Mode
OFF
when inverter is in Stop Mode
Valid for outputs:
11, 12
Required settings:
(none)
Notes:
The inverter outputs the [RUN] signal whenever the 
inverter output exceeds the start frequency specified 
by parameter B_82. The start frequency is the initial 
inverter output frequency when it turns ON.
Example (default output configuration 
shown—see page 
RY
+
See I/O specs on page 
12 11
L
H O OI
FM CM2
RU
Inverter output 
terminal circuit