Eaton Electrical 9130 User Manual

Page of 120
OPERATION
Eaton
®
 9130 UPS (700–3000 VA) User's Guide  
S
  164201718 Rev 2
 www.powerware.com
48
Setting Power Strategy
On the High Efficiency setting, the UPS operates normally on Bypass,
transfers to inverter in less than 10 ms when utility fails, and transfers
back to Bypass in 1 minute after utility returns. The 
 indicator
illuminates when the UPS transfers to Bypass.
NOTE  High Efficiency operation is available after one minute of stable power.
To set the power strategy:
1.
Press any button to activate the menu options, then select
SETTINGS, USER SETTINGS, and POWER STRATEGY.
2.
Select HIGH EFFICIENCY or NORMAL, and ENTER to confirm.
Configuring Bypass Settings
The following settings are available for configuring Bypass operation.
Transfer to Bypass When Overload. The default forces a transfer to Bypass
when any overload condition occurs. You can configure the setting for a
delayed transfer, with the amount of delay determined by the amount of
overload, as shown in Table 19 on page 84.
Bypass Voltage Low Limit. The default disables a transfer to Bypass if the
measured bypass voltage level is below the nominal output voltage
minus 15%. You can configure the setting for another percentage of
nominal. This setting can be overruled by the “Qualify Bypass” setting.
Bypass Voltage High Limit. The default disables a transfer to Bypass if the
measured bypass voltage level is above the nominal output voltage
plus 10%. You can configure the setting for another percentage of
nominal. This setting can be overruled by the “Qualify Bypass” setting.
Qualify Bypass. The default allows a transfer to Bypass only when Bypass
is within the following specifications:
S
Bypass voltage is between the “Bypass Voltage Low Limit” and
“Bypass Voltage High Limit” settings.
S
Bypass frequency is within nominal frequency ±5 Hz.
S
The inverter is synchronized with Bypass when the “Unsynchronized
Transfers” setting is disabled.