88
Table 23. Battery Runtimes (in Minutes) at 100% Load (Rack Models)
Model
Internal Batteries
+ 1 EBM
+ 2 EBMs
+ 3 EBMs
+ 4 EBMs
PW9130L700R-XL2U
9
41
72
105
130
PW9130L1000R-XL2U
5
30
55
83
108
PW9130G1000R-XL2U
PW9130i1000R-XL2U
PW9130G1000R-XL2UEU
PW9130G1000R-XL2UAU
7
29
51
81
98
PW9130L1500R-XL2U
5
23
48
67
91
PW9130i1500R-XL2U
PW9130G1500R-XL2UAU
5
24
44
72
89
PW9130L2000R-XL2U
6
33
59
88
112
PW9130G2000R-XL2U
PW9130i2000R-XL2U
PW9130G2000R-XL2UEU
PW9130G2000R-XL2UAU
6
33
59
88
119
PW9130L2500R-XL2U
PW9130G2500R-XL2U
PW9130G2500R-XL2UEU
4
26
47
71
95
PW9130L3000R-XL2U
3
20
36
53
71
PW9130G3000R-XL2U
PW9130i3000R-XL2U
PW9130G3000R-XL2UEU
PW9130G3000R-XL2UAU
3
18
34
53
69
NOTE  Battery times are approximate and vary depending on the load configuration and battery charge.