Eaton Electrical 9130 User Manual

Page of 120
SPECIFICATIONS
Eaton
®
 9130 UPS (700–3000 VA) User's Guide  
S
  164201718 Rev 2
 www.powerware.com
90
Table 25. Battery
Internal Batteries
EBMs
Rackmount
Configuration
700–1000 VA models:  36 Vdc (3 12V, 9 Ah)
1500 VA models:  48 Vdc (4 12V, 9 Ah)
2000–3000 VA models:  72 Vdc (6 12V, 9 Ah)
PW9130N1000R-EBM2U:  36 Vdc (2x3 12V, 9 Ah)
PW9130N1500R-EBM2U:  48 Vdc (2x4 12V, 9 Ah)
PW9130N3000R-EBM2U:  72 Vdc (2x6 12V, 9 Ah)
Tower
Configuration
700 VA models:  24 Vdc (2 12V, 9 Ah)
1000 VA models:  36 Vdc (3 12V, 9 Ah)
1500 VA models:  48 Vdc (4 12V, 9 Ah)
2000–3000 VA models:  96 Vdc (8 12V, 9 Ah)
PW9130N1000T-EBM:  36 Vdc (2x3 12V, 9 Ah)
PW9130N1500T-EBM:  48 Vdc (2x4 12V, 9 Ah)
PW9130N3000T-EBM:  96 Vdc (2x8 12V, 9 Ah)
Fuses
Not applicable
(4) 30A/125 Vdc fuses per EBM
Type
Sealed, maintenance-free, valve-regulated, lead-acid,
with minimum 3-year float service life at 25°C (77°F)
Monitoring
Advanced monitoring for earlier failure detection and warning
Recharge Time
(to 90%)
Internal batteries:  3 hours
1 EBM:  9 hours; 2 EBMs:  15 hours; 3 EBMs:  21 hours; 4 EBMs:  27 hours
Battery Port
External three-pole Anderson connector on UPS for connection to EBM