APC 66123 User Manual

Page of 16
12 - 3402230800/AC
 
Configuration of the JBUS/MODBUS communication parameters
 
 
◗  Use the cord supplied with the card
◗  Connect the card to a computer
◗  Use a terminal emulator such as HyperTerminal
TM
 with these settings
"Echo typed characters locally" option: disabled
◗  Check that UPS power is on.
◗  Type MGEUPS (or mgeups).
The main configuration menu is displayed::
◗  Press the 5 key (Jbus configuration).
The Jbus configuration  menu is displayed:
Through settings port
Bits per second
Data bits
Stop bits
Parity
Flow control
9600
8
1
none
none
APC by Schneider Electric
Network Management Card & Modbus/Jbus
Release : AB.build_5_0_7
1 : Reset
2 : Network configuration
3 : Set Login Password to Default
4 : Return to Default Configuration
5 : Jbus configuration
6 : Sensor configuration
0 : Exit
Jbus settings
1 : Display Jbus settings
2 : Modify Jbus settings
3 : Display Jbus diagnostics
4 : Reset  Jbus diagnostics
5 : Return to Jbus Default Configuration
6 : Display Jbus frames
0 : Exit
66102
Settings/Sensor
ETHE
RNET
100M           10
M
UPS dat
a    RS2
32
On = Lin
k
Blink =
 Act
ETHERNET
66103
UPS data    R
S232
100M      
     10M
66103
UPS data   
 RS232
100M           
10M
UPS
Connect the RS232 link to a
terminal
(Microsoft Hyper terminal)