D. Appliance Certification
This appliance is design certified by Omni International un-
der the 
ANSI Z21.60b-2004 or CSA 2.26b-2004, Decora-
tive  Appliances  for  Installation  in  Solid-fuel  Burning 
Fireplaces.  Installation  and  the  provisions  for  combustion 
and ventilation air must conform to the 
National Fuel Gas 
Code, ANSI Z223.1/NFPA 54, or the CSA B149.1, Natural 
Gas and Propane Installation Code.
• 
This  appliance  must  have  a  screen  in  place  while  the 
appliance is in operation and, unless other provisions for 
combustion  air  are  provided,  the  screen  shall  have  an 
opening for introduction of combustion air.
•  Solid  fuels  shall  not  be  burned  in  a  fireplace  where  a 
decorative appliance is installed.
•  If glass doors are present, the 
glass doors must be fully 
opened while appliance is in operation.
Do NOT use this appliance if any part has been under 
water.  Immediately  call  a  qualified  service  technician 
to inspect the appliance and to replace any part of the 
control  system  and  any  gas  control  which  has  been 
under water.
WARNING
E. Gas Supply Connection
A 3/8 in. flared fitting has been installed on the gas valve 
inlet at the factory. Ensure fittings are of the appropriate size 
and type on the gas line connection. If the tubing has to be 
cut to length be sure to use the proper cutting and flaring 
tool. Also, be careful not to crimp the tubing while bending. If 
the tubing becomes crimped, do not use for installation. 
Gas resistant pipe compound must be used on all threaded 
male connections to ensure a tight seal.
F.  Gas Pressure
Proper input pressures are required for optimum appliance 
performance. Gas line sizing requirements need to be made 
following 
NFPA51.
Fire Risk
Explosion Risk
Verify inlet pressures.
•  High  pressure  may  cause  overfire 
condition.
•  Low pressure may cause explosion.
Install  regulator  upstream  of  valve  if  line 
pressure is greater than /2 psig.
WARNING
Fire Risk
Explosion Risk
High pressure will damage valve.
•  Disconnect gas supply piping BEFORE 
pressure testing gas line at test pressures 
above /2 psig.
•  Close the manual shutoff valve BEFORE 
pressure testing gas line at test pressures 
equal to or less than /2 psig.
WARNING
•  Gas Supply Pressure: Minimum inlet gas supply pressure 
must be 7.0 in. W.C. for natural gas or  in. W.C. for LP 
gas for the purpose of input adjustment. Maximum inlet 
gas pressure must not exceed 0.5 in. W.C. for natural 
gas or  in. W.C. for LP gas. The gas line supplying the 
appliance must be sufficient size to furnish the appropriate 
supply pressure to the appliance while operating in the 
“High” setting. 
•  Pressure tap screws must be closed before turning gas 
on to the appliance.
•  Gas Line Pressure Test: Perform pressure test according 
to state and local code (if pressure exceeds /2 in. psi (.5 
kPa)) before appliance is connected. Be sure to release 
air pressure from the gas line before connection is made 
to the appliance. Excessive pressure will damage the gas 
control and may cause a gas leak.
•  Gas Leak Test: Make sure the gas connections are tight. 
Turn on the gas and coat each joint with a non-corrosive 
gas leak check solution. Air bubbles will form indicating 
any leaks. DO NOT USE A FLAME OR ANY TYPE OF 
IGNITION SOURCE TO CHECK FOR LEAKS. All leaks 
must be corrected before proceeding with installation.
•  The appliance must only be installed in a solid-fuel burning 
fireplace with the flue damper clamped open according 
to Tables  and 2. The fireplace must be constructed of 
non-combustible material.
•  The minimum permanent free opening (in square inches) 
that must be provided by the fireplace chimney or damper 
to vent the flue gases is provided in Tables 1 and 2. If the 
free opening is smaller than the specified area, do not use 
this appliance.
•  The damper must be removed or fixed in a manner in 
which will secure it open. Some jurisdictions require the 
damper to be removed or permanently welded fully open. 
Check with state and local codes.
•  Be sure that the chimney is completely unobstructed to 
ensure proper ventilation of flue gases including carbon 
monoxide  (CO).  CO  (a  poisonous  gas)  is  tasteless, 
odorless,  colorless  and  undetectable  without  proper 
equipment.
•  Refer to Table 3 to determine minimum fireplace opening 
requirements before proceeding.