NOTE: The following requirements reference various 
Massachusetts and national codes not contained in this 
document.
For all side wall horizontally vented gas fueled equipment 
installed in every dwelling, building or structure used in whole 
or in part for residential purposes, including those owned or 
operated by the Commonwealth and where the side wall 
exhaust vent termination is less than seven (7) feet above 
finished grade in the area of the venting, including but not 
limited to decks and porches, the following requirements 
shall be satisfied:
Installation of Carbon Monoxide Detectors
At the time of installation of the side wall horizontal vented 
gas fueled equipment, the installing plumber or gas fitter shall 
observe that a hard wired carbon monoxide detector with an 
alarm and battery back-up is installed on the floor level where 
the gas equipment is to be installed. In addition, the installing 
plumber or gas fitter shall observe that a battery operated or 
hard wired carbon monoxide detector with an alarm is installed 
on each additional level of the dwelling, building or structure 
served by the side wall horizontal vented gas fueled equip-
ment. It shall be the responsibility of the property owner to 
secure the services of qualified licensed professionals for the 
installation of hard wired carbon monoxide detectors.
In the event that the side wall horizontally vented gas fueled 
equipment is installed in a crawl space or an attic, the hard 
wired carbon monoxide detector with alarm and battery back-
up may be installed on the next adjacent floor level.
In the event that the requirements of this subdivision can not 
be met at the time of completion of installation, the owner shall 
have a period of thirty (30) days to comply with the above 
requirements; provided, however, that during said thirty (30) 
day period, a battery operated carbon monoxide detector with 
an alarm shall be installed.
Approved Carbon Monoxide Detectors
Each carbon monoxide detector as required in accordance 
with the above provisions shall comply with NFPA 720 and 
be ANSI/UL 2034 listed and IAS certified.
Signage
A metal or plastic identification plate shall be permanently 
mounted to the exterior of the building at a minimum height 
of eight (8) feet above grade directly in line with the exhaust 
vent terminal for the horizontally vented gas fueled heating 
appliance or equipment. The sign shall read, in print size no 
less than one-half (1/2) inch in size, “GAS VENT DIRECTLY 
BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.”
G.  Requirements for the Commonwealth of     
      Massachusetts
Inspection
The state or local gas inspector of the side wall horizontally 
vented gas fueled equipment shall not approve the installa-
tion unless, upon inspection, the inspector observes carbon 
monoxide detectors and signage installed in accordance with 
the provisions of 248 CMR 5.08(2)(a) 1 through 4.
Exemptions
The following equipment is exempt from 248 CMR 5.08(2)(a) 
1 through 4:
The equipment listed in Chapter 10 entitled “Equipment 
Not Required To Be Vented” in the most current edition of 
NFPA 54 as adopted by the Board; and 
Product Approved side wall horizontally vented gas fueled 
equipment installed in a room or structure separated from 
the dwelling, building or structure used in whole or in part 
for residential purposes.
MANUFACTURER REQUIREMENTS
Gas Equipment Venting System Provided
When the manufacturer of Product Approved side wall 
horizontally vented gas fueled equipment provides a vent-
ing system design or venting system components with the 
equipment, the instructions provided by the manufacturer for 
installation of the equipment and the venting system shall 
include:
Detailed instructions for the installation of the venting sys-
tem design or the venting system components; and 
A complete parts list for the venting system design or 
venting system.
Gas Equipment Venting System NOT Provided
When the manufacturer of a Product Approved side wall hor-
izontally vented gas fueled equipment does not provide the 
parts for venting the flue gases, but identifies “special vent-
ing systems”, the following requirements shall be satisfied by 
the manufacturer:
The referenced “special venting system” instructions shall 
be included with the appliance or equipment installation 
instructions; and 
The “special venting system” shall be Product Approved 
by the Board, and the instructions for that system shall 
include a parts list and detailed installation instructions.
A copy of all installation instructions for all Product Approved 
side wall horizontally vented gas fueled equipment, all vent-
ing instructions, all parts lists for venting instructions, and/or 
all venting design instructions shall remain with the appli-
ance or equipment at the completion of the installation.
See Gas Connection section for additional Common-
wealth of Massachusetts requirements.