START-UP PROCEDURE FOR ARMSTRONG SERIES EHU-700 HUMIDIFIERS
The following steps should be performed on all newly installed Series EHU-700 Humidifiers to ensure
that the humidifier and the entire humidification system functions correctly.
BEFORE TURNING ON THE POWER
Figure 14-1
1)  Examine the wiring and the components
in the electrical compartment.
2)  Check for any loose wires or quick-
connect terminals that may have been
pulled loose.
3)  Using a screwdriver, TIGHTEN ALL
SCREW TERMINALS on the power 
supply terminal block, ground lug, and 
contactor (Figure 14-1).
Make sure all steam generator tank 
connections are tight. Remember, a 
loose joint is a HOT joint and could be a
fire hazard!
4)  Locate the low voltage terminal block
(Figure 14-1).
Verify that an airflow switch is 
connected between terminals 9 and 15
or that there is a jumper installed. If an
airflow switch is installed, ensure that 
there is airflow.
Verify that a high limit stat is connected 
between terminals 10 and 14 or that a 
jumper is installed.
5)  Turn on the water supply - Check for 
leaks.
TURN ON POWER AT THE CIRCUIT BREAKER
6)  The following should happen:
a)  The Demand Mode and Tank Off lights will be illuminated. The stat demand will be 
displayed.
b)  If the stat demand displayed is greater than 35%, the Tank Off light will go out and a few
seconds later the Fill Light will go on. The unit will begin to fill.
14
Current 
Transformers
Contactors
Power Supply
Terminal Block
Low Voltage
Terminal Block