Sterling XXX10-80 User Manual

Page of 112
10-Pump, 80-Station Controller           Chapter 4: Operation 
54 
 
•  Enter the alphanumeric password. 
Each digit appears as an “
*
” as you touch it. Press 
↵ when complete. 
If you have lost the password(s), contact the manufacturer for assistance. 
Once you have logged on, the password remains active until you log off or the password 
expires. (Setup personnel at your facility control the number of minutes before the password 
expires.) While the password is active, you can continue to carry out password-protected 
tasks without reentering the password. If the timer expires, the controller goes to the Station 
Status screen and you must reenter the password to continue working. 
When you have finished any tasks that require the password, you should log off. (If you 
forget to do this, the controller will log you off when the password expires.) To log off: 
1.  Go to System Setup. 
2.  Touch Log Off on the right of the screen. 
The Station Status screen appears. 
Enabling and Disabling Stations and Pumps 
When a station or pump is disabled, the controller does not attempt to use it and ignores any 
alarms that occur for it. Disabling a station or pump at the controller’s screen is similar to 
bypassing a station with its bypass switch. Enabling a station or pump makes it available for 
use. (For a station to be available for the system, it must be enabled at the controller’s screen 
and its bypass switch [if present] must be in the “0” position.) 
To enable or disable a station (or pump): 
1.  Go to the Station Status (or Pump Status) screen, if needed. 
To reach this screen from any other screen, touch Stations (or Pumps) on the 
right-hand side of the screen. 
Each disabled station (or pump) has an icon with a status of “offline” (silver). All 
other statuses are enabled statuses. 
2.  Touch the icon for the station (or pump) briefly. 
The station (or pump) switches to the new state, as indicated by the color of its icon. 
3.  If the Station n Operator (or Pump n Setup) screen appears when you touch the icon, 
then you have kept your finger on the screen too long. Touch Stations (or 
Pumps
) to return to the Status screen and try again.