Instruction Manual
Plasma Display Electric Pop-Up Lift
13
WIRING EXAMPLES
The information on the following pages cover the most common wiring options:
Pushbutton
Extend and Retract Terminals to be Triggered By 
Separate Dry Contacts
Remote (RC-10)
12 Volt out supply
24 Volt out supply
Two dry contact closures
Voltage Sensing
Pushbutton
Wire for pushbutton operation as follows:
1.
Install a wire between terminal 5 (extend/retract common) and 
ground terminal 3 (see Figure 16).
2.
Connect one wire from pushbutton to terminal #4 
(12 VDC power supply) and the other wire from the pushbut-
ton to terminal #6 (extend/retract) (see Figure 17).
With the unit plugged in, push the button once and the unit should 
extend. Push the button during travel and the unit will stop at that 
location. Push the button after the unit is extended or stopped in 
mid-travel and the unit will retract.
Extend and Retract Terminals to be Triggered By 
Separate Dry Contacts
These terminals can be used with a wall switch or a separate set of 
dry contacts for dedicated extend and dedicated retract. Momentary 
contacts are preferable.
NOTE: The connection between the ground (#13) and any other 
terminal connection must be broken (open) before completing the 
next circuit.
1.
Connect the common to terminal #13 (see Figure 18).
2.
Connect the extend to terminal #11 (see Figure 19).
3.
Connect the retract to terminal #12 (see Figure 20).
Completing the circuit between terminal #13 and terminal #11 will 
cause the unit to extend to the show position (see “Adjust Vertical 
Travel” on page 11 to chang
e height setting). Completing the cir-
cuit between terminal #13 and terminal #12 will cause the unit to 
retract to the closed position.
Figure 16.  12 Volt Supply Jumper
Figure 17.  Pushbutton Wires
Figure 18. Common for Extend and Retract Contacts 
Common
Retract
Figure 19.  Extend Contact Wiring
Service Extend
Extend
Figure 20.  Retract Contact Wiring