 Warning
Fluid Cooler Cleaning:
Any evaporative-type fluid cooler must be thoroughly cleaned on a 
regular basis to minimize the growth of bacteria, including Legionella 
Pneumophila, to avoid the risk of sickness or death. Service personnel
must wear proper personal protective equipment during decontami-
nation. Do NOT attempt any service unless the fan motor is locked
out.
Operators of evaporative cooling equipment, such as closed circuit fluid 
coolers, should follow maintenance programs which will reduce to an ab-
solute minimum the opportunity for bacteriological contamination. Public 
Health Service officials have recommended that “good housekeeping” 
procedures be followed, such as: regular inspections for concentrations 
of dirt, scale, and algae; periodic flushing and cleaning; and the following 
of a complete water treatment program including biocidal treatment.
The visual inspection should take place at least once a week during the 
operating  season.  The  periodic  flushing  and  cleaning  should  be  done 
before and after each cooling season, but in any event at least twice a 
year. The drift eliminators, easily accessible surfaces and the coil should 
be flushed by use of a moderate-pressure water nozzle, being careful not 
to cause physical damage. A reliable water treatment program should be 
installed and maintained. Filtration devices may be employed to reduce 
the suspended solids concentrations, thus increasing the effectiveness 
of the water treatment program. See Fluid Cooler Startup instructions on 
page 12.
Blowdown:
A  fluid  cooler  cools  water  by  continuously  causing  a  portion  of  it  to 
evaporate. Although the water lost by evaporation is replenished by the 
makeup  system,  it  exits  the  tower  as  pure  water—leaving  behind  its 
burden of dissolved solids to concentrate in the remaining water. Given 
no means of control, this increasing concentration of contaminants can 
reach a very high level.
In order to achieve water quality which is acceptable to the fluid cooler,  the 
selected water treatment company must work from a relatively constant 
level of concentrations. This stabilization of contaminant concentrations 
is usually accomplished by blowdown, which is the constant discharge 
of a portion of the circulating water to waste. As a rule, acceptable levels 
on which to base a treatment schedule will be in the range of 2-4 con-