6.   Attach process fluid supply and return piping to the coil. Standard field 
piping connection is an NPT male connection at the coil. A flanged 
connection requires a gasket between the fluid cooler and the fluid 
supply piping. 
For welded connections protect adjacent areas from excessive heat
and sparks or damage may occur.
7.   Wire  motor(s)  and  recirculation  pump(s)  in  accordance  with  wiring 
diagram.
For maintenance/safety purposes, SPX Cooling Technologies recom-
mends a lockout type disconnect switch for all mechanical equipment.
In addition to a disconnect switch, the motor should be wired to main 
power supply through short circuit protection, and a magnetic starter 
with overload protection.
Motor Wiring
Wire motor leads as shown on the motor nameplate matching the supply 
voltage. Do not deviate from the motor nameplate wiring.
Either  of  following  symbols  may  be  shown  on  the  motor  nameplate  – 
Δ, Δ Δ, 
Y
, or 
YY
. These symbols represent how the motor is constructed on 
the inside and in no way have anything to do with a Delta or Wye electrical
distribution system serving the motor.
When using a starter:
•  Set motor overload protection to 110% of motor nameplate amps.
This setting allows the fan motor to operate during cooler weather. 
During cooler weather it is common for the motor to draw 6 to
10% higher than nameplate amps. High amps are common during
tower commissioning when the tower is dry and the ambient air 
temperature is cool.
•  Do not start the motor more than
six times per hour. Short cycling 
the tower will cause fuses, breakers or O.L.s to operate and will 
decrease motor life.
 Caution
 Warning
Installation