Caution
Motor Load
1. The corrected horsepower should be close to but not exceed the contract 
horsepower specified (see page 2). Determine corrected horsepower 
with this equation:
Actual volts and amperage must be obtained with the fan running and the 
specified rate of water flowing over the tower after the motor and Geareducer 
have reached operating temperature (approximately 30 minutes of opera-
tion).
2. The blade pitch can be changed to obtain contract horsepower. A one 
degree pitch change will change the power about eight horsepower. If 
blades are repitched, follow pitching and fastener tightening instructions 
detailed in the  Fan Assembly section of this manual.
Measurements taken on motors operating with Variable Frequency 
Drive controls may read up to 15% high from errors in measuring the 
approximated sine wave. Instruments capable of measuring a squared 
off wave form accurately should be used for measuring power in this 
situation.
When checking and/or changing blade pitch or cycling fan in normal 
operation, do not exceed 30 sec/hour total motor starting time as mo-
tor may be overheated.
Service
When contacting your Marley sales representative for repair or replacement 
parts, please refer to the tower serial number.
Replacement blades can be installed without rebalancing. The fan series—
HP7i—and diameter are required when ordering replacement  parts.
If rebalancing is required, return the fan hub to Marley for factory rebal-
ance.  Obtain  a  Customer  Return  Material  tag  from  your  Marley  sales 
representative.
  VOLTS
=  Nameplate Volts
  AMPS
=  Nameplate Amperage
  HP
=  Nameplate Horsepower
  DENSITY
=  Design Air Density
  HP
=  Corrected Horsepower
  VOLTS
=  Actual Volts
  AMPS
=  Actual Amperage
  DENSITY
=  Actual Air Density
VOLTS
A
 × AMPS
A
 × DENSITY
D
VOLTS
N
 × AMPS
N
 × DENSITY
A
  
HP
 =
× 
 HP
N
Manual 92-1471E