NetworkAIR Rack Air Removal Unit Installation
How to Communicate Using the A-Link
The Rack Air Removal Unit can be used with an APC Environmental Management System that can 
monitor and control the unit. Connect the APC Environmental Management System any Rack Air 
Removal Units by using the in and out A-Link connections.
How to connect to the A-Link
The Rack Air Removal Unit has two connections (IN and OUT) for linking several devices together 
using the A-Link. The Rack Air Removal Unit must be given an address to communicate with the 
APC Environmental Management System. The address DIP switch is recessed inside the space 
marked A-Link Address. Use a small tool such as a pocket screwdriver to set the DIP switch to the 
correct position. 
To remotely monitor the Rack Air Removal Unit: 
1. Set the second, third, and fourth DIP switches to 
give the Rack Air Removal Unit a unique A-Link 
address between one and eight, according to the 
chart.
Warning
Remove power from the Rack Air Removal Unit before setting DIP switches or 
connecting other devices.