MGD Series Gas Furnace                                                                                        Installation Instructions 
Heat Controller, Inc. Jackson, MI 49203                                              MGD Installation Instructions     14 
 
 
Reference: NFPA No.  54, ANSI Z 223.1 National Fuel Gas Code 
Table shows 4% Input Reduction per 1,000 feet elevation 
For Canadian High Altitude (2,000-4,500 feet), reduce gas pressure to burner manifold (manifold Ps.) to 3.0” W.C. and 9.0” W.C. for LP (Propane) Gas