Therma-Stor Products Group 300 Manual De Usuario

Descargar
Página de 11
3
www.thermastor.com • sales@thermastor.com
Toll-Free 1-800-533-7533
2.3 Electrical Requirements
The Phoenix 300 can be plugged into a grounded 5 Amp 
circuit. At 80°F, 60% RH, it draws .e Amps. Due to the 
high percentage of a 5 Amp circuit’s capacity that the 
unit uses, the circuit should be dedicated to running it 
only. Amp draw decreases at lower loads and increases 
at higher loads. At extremely high loads, a 20 Amp circuit 
may be required.
The unit briefly draws more amps to start if it has been 
stored in a cold area. This may cause a 5 Amp circuit 
breaker to trip. A 20 Amp circuit is recommended in such 
situations. Some models have a time delay to delay the 
compressor start about 2 minutes after the power switch 
is turned on. This reduces the unit’s starting amp draw by 
starting the blower and compressor at different times.
If an extension cord is required, it must have a minimum of 
2 gauge conductors if 25 feet long or less and 0 gauge 
conductors if greater than 25 feet long.
2.4 Condensate Removal
The Phoenix 300 is equipped with an internal condensate 
pump to remove the water that is condensed during 
dehumidification. This allows the condensate to be 
pumped 30’ with the attached hose. If the condensate 
must be pumped more than 20 feet above the unit, a 
second pump must be added to relay the condensate.
2.5 Ducting
A detachable 0” round exhaust collar is supplied that 
will allow a 0” round flexible duct to be attached to the 
Phoenix 300 outlet. The duct and collar may be quickly 
attached to the Phoenix 300 by sliding the 4 collar tabs 
into the slots around the blower outlet and rotating the 
collar clockwise. It may be quickly removed to transport 
the unit more easily.
2.6 Power Switch
The power switch (on left side of hour meter) lights up 
when the unit is turned on. The unit will continue to run 
in all conditions until the switch is turned off; there is no 
dehumidistat.
2.7 Pump Purge Switch
This switch (on right side of hour meter) minimizes the 
water left in the condensate pump reservoir for moving or 
storage. Pressing and holding the pump purge switch will 
cause the condensate pump to run. Hold the switch in 
until the flow from the condensate hose stops.
2.8 Pump Fail Light
If the condensate pump fails, water draining into the pump 
reservoir will fill above its normal level. A safety float 
switch will then turn on the pump fail light (located next 
to the pump purge switch) and stop the compressor. This 
prevents water from overflowing and wetting the floor. The 
safety switch will not allow the compressor to restart until 
water has been removed from the pump reservoir.
2.9 Hour Meter
The digital hour meter measures the cumulative time that 
the unit is turned on to tenths of an hour. It stores its 
total when the unit is unplugged; the previous total will be 
displayed when the unit is next turned on. It resets to zero 
after 99,999.9 hours of operation.
2.10 Defrost Control Adjustment
When the Phoenix 300 is used in a cool area, frost will 
form on the cooling coil as it dehumidifies. When enough 
frost forms, the defrost thermostat will initiate the 
timed defrost cycle. The cycle periodically turns off the 
compressor while allowing the blower to run. The frost is 
melted by the air that the blower draws through the cooling 
coil.
The defrost cycle is automatic and designed for optimum 
performance above 50°F. If the unit is used in an area that 
is below 50°F for more than 2 hours, adjustment of the 
defrost timer is recommended to improve performance 
(see Sec. 2.0).
DRYING TIP: Air’s ability to absorb moisture from wet 
surroundings and the Phoenix 300’s ability to remove 
moisture from that air is greatly improved at higher 
temperatures. We recommend that the area to be dried be 
heated to over 70°F if possible. Less drying time will be 
required and efficiency will improve.
To adjust the defrost timer:
.   Unplug the unit.
2.   Remove the front cover (6 screws).
3.   The timer is fastened to the right inside panel. Every 
fourth peg around the dial is pushed out from the dial 
center except one section with 5 pegs out in a row. 
See figure . Each fourth “out” peg represents 5 
minutes of compressor “off” time during every hour 
that the unit is in the defrost cycle.
4.   To improve performance below 50°F, the compressor 
“off” time must be increased to 30 minutes per hour 
to allow the frost to completely melt. To do this, push 
the pegs out from the dial center so that the pegs 
alternate with 2 toward the center, then 2 out from 
the center, all the way around the dial except for the 
section now with 6 pegs out in a row (see Fig. ).