2.5  Relay Connection 
All poles of the  three relays are available at the modular connector J2  (see  Figure  2-2  for details). J2 is a 9-
position variant of the high voltage modular connector used for power input. Each terminal can accommodate a 
wire size 12 to 24 AWG. 
 
Insert this face of connector
into mating connector on
control circuit board.
R2  NO
R2  C
R3 NO
R1  NC
R3  NC
R1  C
R2  NC
R1  NO
1
9
R3  C
 
Figure 2-2 Relay Connector 
 
To install the wiring for the relays, disconnect the connector from the header on the PCB. Strip the insulation of 
each wire back  approximately  1/4 in. (6.5 mm), insert the bare wire into the terminal and tighten the screw 
clamp. Ensure that the wire cannot easily be pulled from the connector.  
 
Note that the panel configuration can designate Relay-1 as an ALARM signal relay. Relay-2 and Relay 3 are 
general purpose in function. 
 
Refer to Table 2-5 for output signals, connector and terminal assignment for all three relays. 
 
Signal Name 
Connector-
Pin Number 
Signal Name 
Connector-
Pin Number 
Signal Name 
Connector-
Pin Number 
Relay 1 NC 
J2-1 
Relay 2 NC 
J2-4 
Relay 2 NC 
J2-7 
Relay 1 NO 
J2-2 
Relay 2 NO 
J2-5 
Relay 2 NO 
J2-8 
Relay 1 Common 
J2-3 
Relay 2 Common 
J2-6 
Relay 2 Common 
J2-9 
Table 2-5 Relay Interface Signals and Connector Assignments