Macurco DVP-120 Manual De Usuario

Descargar
Página de 37
Revision 0.07 
30 
3.3.7.3  Timed Day Selection 
Z  1    G  r  o  u  p    1    T  i  m e  d 
D a  y  s  :  1      W e  e  k  d  a  y  s 
Figure 3-43 Timer Days Selection 
Valid entries are: 
– 
1 Weekdays, Monday thru Friday, (default) 
– 
2 Weekends, Saturday and Sunday 
3.3.7.4  Start Time 
Z  1    G  r  o  u  p    1    T  i  m e  d 
S  t  a  r  t    T  i  m e  :  0  7  :  0  0 
Figure 3-44 Start Time Selection 
The start time is entered in 24-hour format and the default value is 07:00 (7:00 AM). 
3.3.7.5  Stop Time 
Z  1    G  r  o  u  p    1    T  i  m e  d 
S  t  o  p    T  i  m e  :    1  8  :  0  0 
Figure 3-45 Stop Time Selection 
The stop time is entered in 24-hour format and the default value is 18:00 (7:00 PM). 
3.3.7.6  Sensor Selection 
Z  1    G  r  o  u  p    1        N O 2 
S  e  n  s  o  r  s  :  0  2  ,  0  4  ,  1  1 
Figure 3-46 Sensor Selection 
Sensors are included or removed from the group by entering the  two-digit channel number. After  a  sensor is 
added or removed the list will be re-sorted so it  does not matter in which order the sensors are added or 
removed. The default is to include all sensors of the specified type. 
 
When the first digit of a sensor number is entered (a leading zero must be entered if the number is less than ten), 
the display will prompt to Add or Remove a sensor from the group. 
 
Z  1    G  r  o  u  p    1        N O 2 
A d  d  /  R  e m o  v  e  :  _  0       
Figure 3-47 Add/Remove sensor prompt 
When the  second digit is entered, the sensor will be added or removed from the control group, provided the 
sensor is of the proper type, NO2 in this example. If the sensor is of the wrong type, or an invalid sensor 
channel number is entered the request will be simply ignored.