COMBUSTION AIR SUPPLY 
For a mobile home installation the stove must be connected to an 
outside source of combustion air. A 2” inside diameter metallic pipe, 
either flexible or rigid, may be attached to the inlet at the stove’s 
rear (refer to figures 5 & 6). A rodent guard (minimum ¼” wire 
mesh)/wind hood must be used at the terminus (refer to figure 7). 
All connections must be secured and airtight by either using the 
appropriately sized hose clamp and/or UL-181-AP foil tape.  
For mobile home installations only: 2” inside diameter pipe may 
be used for the first 5 feet of combustion air supply run. From 5 to 
10 feet use 2 ¾” inside diameter pipe. No combustion air supply 
may exceed 10 feet. 
Sources of Outside Combustion Air 
a. In 
fireplaces 
• Chimney 
top. 
• 
Ash clean out door. 
b. For 
freestanding 
installations 
• 
A hole in floor near stove rear terminating only in a 
ventilated crawl space. 
• 
A hole in the wall behind the stove. 
WHEN OUTSIDE AIR IS NOT USED 
If outside air is not used, it is important that combustion air is easily 
available to the air inlet. A closeable outside air register can be 
used in tightly insulated homes. In insert installations, flashing vents 
should not be restricted. The flashing should not necessarily seal 
the fireplace face. 
VENTING 
The Breckwell P2000 is certified for use with listed TYPE L-Vent, 3” 
or 4” diameter in size. The stove was tested with Simpson Duravent 
brand. Class “A” chimney is not required. Refer to the instructions 
provided by the vent manufacturer, especially when passing 
through a wall, ceiling or roof. 
This is a pressurized exhaust system. We suggest sealing all vent 
connector joints with 500
°F (260°C) RTV silicone sealant to ensure 
consistent performance and to avoid smoke spillage. We also 
suggest that all horizontal connector joints be sealed with UL-181-
AP foil tape. 
FOLLOW L-VENT CHIMNEY MANUFACTURER’S 
INSTALLATION INSTRUCTIONS. 
DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING 
ANOTHER APPLIANCE. 
DO NOT INSTALL A FLUE DAMPER IN THE EXHAUST 
VENTING SYSTEM OF THIS UNIT. 
INSTALL VENT AT CLEARANCES SPECIFIED BY THE VENT 
MANUFACTURER. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 