2700-I  WOOD INSERT (ACT)
INSTALLATION IN CANADA
 
  
MASONRY and HEAT-CIRCULATING
(INSTALLATIONS INTO FACTORY-BUILT FIREPLACES ARE 
PROHIBITED IN CANADA)
Whether  installed  in  a  masonry  or  heat-circulating  fire-
place, this fireplace insert must be installed with a continu-
ous chimney liner of 6 inches (152mm) diameter extending 
from  the  fireplace  insert  to  the  top  of  the  chimney.  The 
chimney  liner  must  conform  to  the  Class    requirements 
of CAN/ULC-S65, Standard for Lining Systems for Exist-
ing Masonry or Factory-Built Chimneys and Vents, or CAN/
ULC-S640, Standard for Lining Systems for New Masonry 
Chimneys.
•  Do  not  remove  bricks  or  mortar  from  fireplace  to 
accommodate insert.  
• To prevent room air passage to the chimney cavity of 
the fireplace seal the damper area around the chimney 
liner with high temperature sealant. 
• The permanent metal warning label provided must be 
affixed to the back of the fireplace with screws or nails 
to the fireplace, in a location readily visible should the 
fireplace insert by removed, stating that the fireplace 
may have been altered to accommodate the insert, and 
must be returned to original condition for use as a con-
ventional fireplace
 LEVELING LEGS 
Remove 
screw
s
1.  Remove the 2 screws already installed on each leg.
2.  Move legs to the desired height.
.  Re-install the screws to secure in place.
Figure 11.2
DOOR HANDLE ASSEMBLY
1.  Install washer on door handle shaft.
2.  Slide door handle through door.
.  Install second washer(s) as shown.
4.  Install key in groove.
5.  Align groove in latch cam with key; slide latch cam over 
shaft.
6.  Install locknut.
7.  Install spring handle turning counter-clockwise to 
desired location on handle.
Locknut 
Door Cross Section 
(example) 
Latch Cam 
Spacing 
Washers
Square Key 
Door Handle 
Spring 
Handle 
Figure 11.1
NOTE:
In Canada when using a factory-built chimney it must be 
safety listed, Type UL 10 HT CLASS "A" or conforming 
to CAN/ULC-S629, STANDARD FOR 650°C FACTORY-
BUILT CHIMNEYS.
CAUTION
•  Do NOT overtighten lock nut.
•  Door handle needs to move smoothly.