Hearth & Home Technologies 2700-I Manual De Usuario

Descargar
Página de 28
2700-I  WOOD INSERT (ACT)
Page 8
September 1, 2008
7007-161H
I
NSTALLATIONS INTO MOBILE HOMES 
Spark Arestor Cap 
Roof Flashing 
Storm Collar 
Joist Shield/Firestop 
Double Wall 
Connector Pipe  
Figure 8.2 - Installing Outside Air Cover Box
Outside Air
Cover Box
Back of
Panel
1.  An outside air inlet must be provided for combustion and 
must remain clear of leaves, debris, ice and/or snow.  It 
must be unrestricted while unit is in use to prevent room 
air starvation which can cause smoke spillage and an 
inability to maintain a fire.  Smoke spillage can also set 
off smoke alarms.
2.  Unit must be secured to the mobile home structure.
Figure 8.1 
CAUTION
Maintain structural integrity of mobile home:
•   Floor, wall, ceiling and/or roof.
Do NOT cut through:
•  Floor joist, wall, studs or ceiling trusses.
• 
Any supporting material that would affect the structural 
integrity.
•  Never install in a sleeping room.
Consumes oxygen in the room.
WARNING
Asphyxiation Risk.
10.  Burn  wood  only.    Other  types  of  fuels  may  generate 
poisonous gases (e.g., carbon monoxide).
11.  If  unit  burns  poorly  while  an  exhaust  blower  is  on  in 
home, (i.e., range hood), increase combustion air.
12.  Installation shall be in accordance with the Manufacturers 
Home & Safety Standard (HUD) CFR 280, Part 24.
1.  An outside air inlet must be provided for combustion.   See 
page 12 for installation information.
2.  Appliance must be secured to the mobile home structure 
by  bolting  the  pedestal  through  hearth  pad  and  into 
floor.  
.  Appliance  must  be  grounded  with  #8  solid  copper 
grounding wire or equivalent and terminated at each end 
with N.E.C. approved grounding device.
4.  Appliance must be installed with an approved UL10 HT 
ventilated chimney connector, UL10 HT chimney, and 
terminal cap with spark arrestor.  Never use a single wall 
connector (stove pipe) in a mobile home installation.  Use 
only double-wall connector pipe, Dura-Vent DVL, Selkirk 
metalbestos DS or Security DL double-wall connector or 
any listed double-wall connector pipe.
5.  In Canada, this appliance must be connected to a 6 inch 
(152mm)  factory-built  chimney  conforming  to  CAN/ULC-
629M, STANDARD FOR FACTORY BUILT CHIMNEYS. 
6.  Follow the chimney and chimney connector manufacturer’s 
instructions when installing the flue system for use in a 
mobile home.
7.  Maintain clearance to combustibles.
8.  Floor  protection  requirements  must  be  followed 
precisely.
9.  Use  silicone  to  create  an  effective  vapor  barrier  at  the 
location where the chimney or other component penetrates 
to the exterior of the structure.
NOTE:    Offsets  from  the  vertical,  not  exceeding  45°,  are 
allowed per Section 905(a) of the Uniform Mechanical Code 
(UMC). Offsets greater than 45° are considered horizontal 
and are also allowed, providing the horizontal run does not 
exceed 75% of the vertical height of the vent. Construction, 
clearance and termination must be in compliance with the 
UMC Table 9C. This installation must also comply with NFPA 
211.
NOTE: Top sections of chimney must be removable to allow 
maximum clearance of 1.5 feet (411cm) from ground level 
for transportation purposes.
WARNING
Do not draw outside combustion air from:
•  Wall, floor or ceiling cavity
•  Enclosed space such as an attic or garage
•  Close proximity to exhaust vents or chimneys.
Fumes or odor may result
Fire Risk.
Asphyxiation Risk.