Mitsubishi Electronics PUHY-P144 Manual De Usuario

Descargar
Página de 326
- 40 -
[
II  Restrictions ]
GB
HWE08040
(4) Wiring method
1)   Indoor/outdoor transmission line
Same as [5] 3.
Shielded cable connection
Same as [5] 1.
2)   Transmission line for centralized control
Same as [5] 4.
Shielded cable connection
Same as [5] 4.
3)   MA remote controller wiring
Same as [5] 1.
When 2 remote controllers are connected to the sys-
tem
Same as [5] 1.
Group operation of indoor units
Same as [5] 1.
4)   M-NET remote controller wiring
Same as [5] 1.
When 2 remote controllers are connected to the sys-
tem
Same as [5] 1.
Group operation of indoor units
Same as [5] 1.
5)   LOSSNAY connection
Same as [5] 4.
6)   Switch setting
Address setting is required as follows.
(5) Address setting method
The outdoor units in the same refrigerant circuit are automatically designated as OC, OS1, and OS2. 
Proce-
dures
Unit or controller
Address 
setting
range
Setting method
Notes
Factory
setting
1
Opera-
tion
with the 
MA re-
mote
control-
ler
In-
door
unit
Main unit
IC
01 to 50
Assign the smallest address 
to the main unit in the group.
ŒAssign an address smaller 
than that of the indoor unit that 
is connected to the M-NET re-
mote controller.
ŒEnter the same indoor unit 
group settings on the system 
controller as the ones that 
were entered on the MA re-
mote controller.
ŒTo perform a group operation 
of indoor units that have differ-
ent functions, designate the 
indoor unit in the group with 
the greatest number of func-
tions as the main unit.
00
Sub unit
Assign sequential num-
bers starting with the ad-
dress of the main unit in 
the same group +1. (Main 
unit address +1, main unit 
address +2, main unit ad-
dress +3, etc.)
MA 
re-
mote 
con-
troller
Main re-
mote con-
troller
MA
No 
settings
required.
-
Main
Sub
remote
controller
MA
Sub 
remote 
controller
Settings to be made ac-
cording to the remote 
controller function selec-
tion
2
Opera-
tion
with the 
M-NET
remote 
control-
ler
In-
door
unit
Main unit
IC
01 to 50
Assign the smallest ad-
dress to the main unit in 
the group.
ŒEnter the indoor unit group set-
tings on the system controller 
(MELANS).
ŒAssign an address larger than 
those of the indoor units that 
are connected to the MA re-
mote controller.
ŒTo perform a group operation 
of indoor units that have differ-
ent functions, designate the 
indoor unit in the group with 
the greatest number of func-
tions as the main unit.
00
Sub unit
Assign sequential num-
bers starting with the ad-
dress of the main unit in 
the same group +1. (Main 
unit address +1, main unit 
address +2, main unit ad-
dress +3, etc.)
M-
NET
re-
mote 
con-
troller
Main re-
mote con-
troller
RC
101 to 
150
Add 100 to the main unit 
address in the group.
ŒIt is not necessary to set 
the 100s digit.
ŒTo set the address to 200, 
set the rotary switches to 
00.
101
Sub
remote
controller
RC
151 to 
200
Add 150 to the main unit 
address in the group.
3
LOSSNAY
LC
01 to 50
Assign an arbitrary but 
unique address to each of 
these units after assign-
ing an address to all in-
door units.
None of these addresses 
may overlap any of the in-
door unit addresses.
00
4
Outdoor unit
OC
OS1
OS2
51 to 100
Assign sequential ad-
dress to the outdoor units 
in the same refrigerantcir-
cuit. The outdoor units 
are automatically desig-
nated as OC, OS1, and 
OS2.(Note)
To set the address to 100, 
set the rotary switches to 50.
00