REPLACING THE INDOOR COIL 
THERMISTOR
REPLACING THE CONTROL BOARD
ELECTRIC SHOCK HAZARD 
WARNING
Disconnect  power  to  the  unit  before 
servicing.  Failure  to  follow  this  warning 
could result in serious injury or death. 
Remove the decorative front cover (see page 29).
Remove all indicated screws below (8 total, see figure 
below).  Remove  the  Discharge  Sensor  and  the  User 
Interface plugs from the control board.
Remove the decorative front cover (see page 29).
Disconnect discharge sensor plug (red)
Disconnect the User Interface plug (white)
Remove the 3 screws indicated below.
Pull control board and mount plate out and disconnect 
the following connectors from it: 
Power, capacitor, thermistors, fan, reversing valve
and heater. 
Remove the hex screw holding the control board to 
its mount plate. Pull out the control board (see figure 
below).
Replace the indoor coil sensor. Ensure to properly clip 
and insulate it at the same location (see figure below). 
Remove the screws indicated at the side and back plate 
(6 total, see figure below). Partially lift the top cover and 
at the same time carefully swing out from the top, the 
back and side plate.
ELECTRIC SHOCK HAZARD 
WARNING
Disconnect  power  to  the  unit  before 
servicing.  Failure  to  follow  this  warning 
could result in serious injury or death. 