HEATING ELEMENT
All heat pumps and electric heat models are equipped 
with    a  heating  element  with  the  exception  of  model 
YS10M10.  The  other  “YS”  and  “ES”  models  are 
equipped  with a 3.3 KW element. The “YM” and “EM” 
models are  equipped with a 4.0 KW element. The “YL” 
and “EL” models  are equipped with a 5.2 KW element. 
The heating element contains a fuse link and a heater 
limit  switch. The fuse link is in series with the power 
supply and will  open and interrupt the power when the 
temperature reaches 199°F or a short circuit occurs in 
the heating element. Once the fuse link separates, a 
new fuse link must be installed.  
NOTE:  Always replace with the exact replacement. 
The heater element has a high limit control. This 
control  is a bimetal thermostat mounted in the top of 
the heating  element. 
Should  the  fan  motor  fail  or  filter  become  clogged, 
the high  limit control will open and interrupt power to 
the heater before  reaching an unsafe temperature 
condition. 
The control is designed to open at 110°F  ±6°F. Test 
continuity  below 110°F or when it is cooled off. 
HEATING ELEMENT (Heat Pump Models) 
The  heating  element  for  the  “Y”  model  is  energized 
by an  outdoor thermistor via the electronic control 
board.  The  outdoor  defrost  thermistor  is  adjusted  at 
a  predetermined temperature of approximately 30 
degrees  Fahrenheit  and  sensed  for  two  consecutive 
minutes,  to  stop  the  compressor  and  turn  on  the 
heating element. 
Heating Element 
Sample
TESTING THE HEATING ELEMENT
Testing of the elements can be made with an ohmmeter  
across  the  terminals  after  the  connecting  wires 
have been  removed. A cold resistance reading of 
approximately 14.5 ohms for the 3.3 KW heater, 11.9 
ohms for the 4.0 KW heater  and 9.15 ohms for the 5.2 
KW heater should be registered.  
DRAIN PAN VALVE 
During  the  cooling  mode  of  operation,  condensate 
which  collects in the drain pan is picked up by the con-
denser fan  blade and sprayed onto the condenser coil. 
This assists in cooling the refrigerant plus evaporating 
the water. 
During the heating mode of operation, it is necessary 
that water be removed to prevent it from freezing during 
cold outside temperatures. This could cause the con-
denser  fan  blade  to  freeze  in  the  accumulated  water 
and prevent it from turning.  
To  provide  a  means  of  draining  this  water,  a  bellows 
type drain valve is installed over a drain opening in the 
base pan. 
This valve is temperature sensitive and will open when 
the outside temperature reaches 40°F. The  valve  will 
close gradually as the temperature rises above 40°F to 
fully close at 60°F.  
Bellows Assembly  
Drain Pan Valve  
COMPONENTS TESTING (continued)
ELECTRIC SHOCK HAZARD 
WARNING
Disconnect  power  to  the  unit  before 
servicing.  Failure  to  follow  this  warning 
could result in serious injury or death.